6 Technical Data
6.2 Specific rated operational data
DC1…20… and DC1…OE1 Variable Frequency Drives
02/20 MN040059EN
www.eaton.com
151
6.2.2 DC1-12…device series
Size
Symbol
Unit
2D3
4D3
7D0NN
7D0FN
7D0NB
7D0FB
011
015
Rated operational current
I
e
A
2.3
4.3
7
7
10.5
15
Overload current for 60 s every 600 s
i
l
A
3.45
6.45
10.5
10.5
15.75
22.5
Overload current for 2.5 s every 600 s
i
l
A
4.03
7.53
12.25
12.25
18.38
26.25
Apparent power at rated operation
230 V
S
kVA
0.92
1.71
2.79
2.79
4.18
5.98
Apparent power at rated operation
240 V
S
kVA
0.96
1.79
2.91
2.91
4.36
6.24
Assigned motor power
at 230 V, 50 Hz
P
kW
0.37
0.75
1.5
1.5
2.2
4
at 220 - 240 V, 60 Hz
P
HP
0.5
1
2
2
3
5
Power side (primary side):
Number of phases
single-phase or two-phase
Rated operating voltage
U
LN
V
200 - 10 % - 240 + 10 %, 50/60 Hz
180 - 264 ±0 %, 48 - 62 Hz ±0 %
Input current (phase current)
I
LN
A
3.7
7.5
12.9
12.9
19.2
29.2
Minimum braking resistance
R
B
Ω
–
–
–
100
50
25
Switching frequency (pulse frequency)
Default Setting
f
PWM
kHz
8
8
8
8
8
8
Setting range
f
PWM
kHz
4 -32
4 -32
4 -32
4 -32
4 -32
4 -24
Voltage Boost (U
Boost
/U
LN
)
Default Setting
%
3
3
3
2.5
2.5
2
Max Value
%
25
25
25
20
20
15
Maximum leakage current to earth
(PE), at U
LN
: 240 V, without motor
I
PE
mA
4.8
4.8
4.8
4.8
4.8
4.7
Efficiency
η
0.95
0.94
0.96
0.96
0.95
0.96
Heat dissipation
At I
e
(150 %)
P
V
W
18.5
45.75
63
63
103.4
160
During no-load running, standby
(locked, without fan)
P
V
W
3.07
3.07
3.07
4.51
4.51
5.16
Fan
–
✓
1)
✓
1)
✓
1)
✓
1)
✓
1)
Size
FS1
FS1
FS1
FS2
FS2
FS3
1) Not with IP66 degree of protection