6 Technical Data
6.8 Radio interference suppression filter
DC1…20… and DC1…OE1 Variable Frequency Drives
02/20 MN040059EN
www.eaton.com
169
6.8 Radio interference suppression filter
Figure 85:
DX-EMC…-FS… (base-mounted filters with prefabricated connection cables) and
DX-EMC… (side-mounting filters) external radio interference suppression filters
DX-EMC… external radio interference suppression filters should always be
installed in the immediate proximity of the corresponding variable frequency
drive. The connection cables between the radio interference suppression
filter and the variable frequency drive should not be longer than 300 to
500 mm if they are installed without screening.
→
The DX-EMC… radio interference suppression filters with an
IP20 degree of protection listed below are intended for
installation in a control panel.
Please enquire for higher degrees of protection.
→
DX-EMC…-
FS
: Base-mounted filter for the specified frame size
DX-EMC…-
L
: Low leakage current
→
For more information and technical data on DX-EMC… radio
interference suppression filters, please refer to the instruction
leaflets IL04012017Z and IL04012018Z.
→
The maximum motor cable lengths for the C1, C2, and C3
interference categories listed below are standardized
recommended values. They apply to the adjustable switching
frequencies (f
PWM
) of 4 to 24/32 kHz (parameter P-17) in the
corresponding ratings.
LINE
L0AD