6 Technical Data
6.2 Specific rated operational data
DC1…20… and DC1…OE1 Variable Frequency Drives
02/20 MN040059EN
www.eaton.com
153
DC1-32… device series
Continue
Size
Symbol
Unit
011
018
024
030
046
Rated operational current
I
e
A
10.5
18
24
30
46
Overload current for 60 s every 600 s
i
l
A
15.75
27
36
45
69
Overload current for 2.5 s every 600 s
i
l
A
18.38
31.5
42
52.5
80.5
Apparent power at rated operation
230 V
S
kVA
4.18
7.17
9.55
11.94
18.30
Apparent power at rated operation
240 V
S
kVA
4.36
7.48
9.96
12.46
19.10
Assigned motor power
at 230 V, 50 Hz
P
kW
2.2
4
5.5
7.5
11
at 220 - 240 V, 60 Hz
P
HP
3
5
7.5
10
15
Power side (primary side):
Number of phases
3
3
3
3
3
Rated operating voltage
U
LN
V
200 - 10 % - 264 + 10 %, 50/60 Hz
180 - 264 ±0 %, 48 - 62 Hz ±0 %
Input current (phase current)
I
LN
A
12.1
20.9
26.4
33.3
50.1
Minimum braking resistance
R
B
Ω
50
25
20
15
10
Switching frequency (pulse frequency)
Default Setting
f
PWM
kHz
8
8
8
8
8
Setting range
f
PWM
kHz
4 -32
4 -24
4 -24
4 -24
4 -24
Voltage Boost (U
Boost
/U
LN
)
Default Setting
%
2.5
2
2
1.5
1.5
Max Value
%
20
15
15
10
10
Maximum leakage current to earth
(touch current), at U
LN
: 240 V, without
motor
I
Touch
mA
7.2
6.8
6.8
6.9
6.9
Efficiency
η
0.96
0.96
0.97
0.97
0.96
Heat dissipation
At I
e
(150 %)
P
V
W
90.2
160
223
304
446
During no-load running, standby
(locked, without fan)
P
V
W
4.51
5.16
5.16
7.54
7.54
Fan
✓
1)
✓
1)
✓
1)
✓
✓
Size
FS2
FS3
FS3
FS4
FS4
1) Not with IP66 degree of protection