Page 35
3 Installation
Wiring of CT & VT Connections, Con’t.
Check to be sure all required CT and VT terminal block and terminal block hood hardware
is available. Do not proceed with installation without the correct CT and VT terminal block
and terminal block hood hardware.
Insulation should be stripped back 3/8 in. for proper connection.
A 1/8 in. flat blade screwdriver should be used to tighten the terminal block screws.
Current and Voltage terminal block hoods are equipped with retaining brackets to retain
the wires in the proper wire channel. To prevent accidental damage to wire insulation while
assembling connector hoods, retaining brackets be securely and properly installed.
The hooded connector, when properly assembled, can be grasped to insert and remove
from terminal block socket. Do not remove terminal blocks by pulling on the wires.
Terminal blocks are polarized and should only be inserted in the proper orientation. To
prevent damage to the equipment or hazardous conditions, care should be taken to orient
the terminal plug correctly with respect to the socket before insertion.
If CT or VT terminal blocks or connector hoods are lost or damaged, contact your Eaton
representative to obtain the correct replacement hardware.
WARNING!
The use of improper CT or VT teminal block hardware may result in severe
injury or death.
Photos of the Power Xpert Meter with hooded connections properly installed are displayed
on the following page.
Содержание Power Xpert PXM 4000
Страница 1: ...User and Installation Manual IM02601004E Power Xpert PXM 4000 6000 8000 ...
Страница 8: ...Page vi IM02601004E www eaton ...
Страница 19: ...www eaton com IM02601004E Page 11 1 Introduction ...
Страница 24: ...Page 16 IM02601004E www eaton ...
Страница 36: ...Page 18 IM02601004E www eaton com 2 Quick Start Guide for the Meter Module ...
Страница 45: ...www eaton com IM02601004E Page 37 3 Installation 3 8 MeterDimensions ...
Страница 46: ...Page 38 IM02601004E www eaton 3 Installation Dimension Con t ...
Страница 47: ...www eaton com IM02601004E Page 39 3 Installation Dimension Con t ...
Страница 48: ...Page 40 IM02601004E www eaton 3 Installation Dimension Con t ...
Страница 53: ...www eaton com IM02601004E Page 45 3 Installation ...
Страница 54: ...Page 46 IM02601004E www eaton 3 Installation ...
Страница 55: ...www eaton com IM02601004E Page 47 3 Installation ...
Страница 56: ...Page 48 IM02601004E www eaton 3 Installation ...
Страница 57: ...www eaton com IM02601004E Page 49 3 Installation ...
Страница 58: ...Page 50 IM02601004E www eaton 3 Installation ...
Страница 59: ...www eaton com IM02601004E Page 51 3 Installation ...
Страница 60: ...Page 52 IM02601004E www eaton 3 Installation ...
Страница 61: ...www eaton com IM02601004E Page 53 3 Installation ...
Страница 62: ...Page 54 IM02601004E www eaton 3 Installation ...
Страница 63: ...www eaton com IM02601004E Page 55 3 Installation ...
Страница 66: ...Page 58 IM02601004E www eaton 3 Installation ...
Страница 75: ...www eaton com IM02601004E Page 67 4 Introduction to Web Server Screens ...
Страница 76: ...Page 68 IM02601004E www eaton 4 Introduction to Web Server Screens ...
Страница 86: ...Page 78 IM02601004E www eaton 5 Introduction to the Local Graphical Display ...
Страница 108: ...Page 100 IM02601004E www eaton 6 Functions on the Web Server Pages ...
Страница 128: ...Page 120 IM02601004E www eaton 7 Functions on the Graphical Display ...
Страница 164: ...Page 156 IM02601004E www eaton 8 Setup on the Web Server Pages ...
Страница 198: ...Page 190 IM02601004E www eaton A MODBUS Communication ...
Страница 242: ...Page 234 IM02601004E www eaton ...
Страница 252: ...Page 244 IM02601004E www eaton D Diagnostics ...
Страница 254: ...Page 246 IM02601004E www eaton D Diagnostics ...