8 Setup on the Web Server Pages
SUBCYCLE DISTURBANCE
The Power Xpert Meter captures subcycle disturbances with its regular metering hardware, which
samples at 30.72 ksps. You can set the dv/dt Threshold and Absolute Threshold for Van, Vbn, Vcn,
Vab, Vbc, and Vca. In addition, you can select the kind of action that will occur when one of the
thresholds has been reached; Capture Waveform, Capture Parameters and/or Send E-mail.
The Absolute Threshold Voltage setting is intended
to trigger on Voltage spikes that exceed the normal
positive and negative peak values, which are typi-
cally 1.4 times the rms line-to-ground Voltage. It is
important to set this threshold safely above the ex-
pected peaks. The Setup page suggests a threshold
that is 20% above the Nominal L-L Voltage (divided
by the PT ratio). For example, a 120V/208V system
has a 120V rms and 170V peak (line-to-ground), and
so a 250V threshold is appropriate (i.e. 208 + 20%).
The dv/dt Threshold setting is entered in dv while the
dt is fixed at the hardware sampling rate. The Setup
page suggests an aggressive threshold. Specifically,
the setup page suggests a threshold that is 5% of
the Nominal L-L Voltage (divided by the PT ratio).
To calculate the volts per microsecond, multiply the threshold Volts by 0.03072. For example, if the
dv/dt Threshold is set at 20V, the Volts per micro second would be 0.744 (i.e. 20V x 0.0372 Msps =
0.744 V/ microsecond).
A 30.72 ksps sampling rate and a pure 120V sine wave would result in a dv of 1.5V per sample at
the zero crossing. A disturbed waveform would have a much higher dv/dt.
Note:
To notify Power Xpert software of subcycle disturbances, select the Send Web Services
Notification box.
Содержание Power Xpert PXM 4000
Страница 1: ...User and Installation Manual IM02601004E Power Xpert PXM 4000 6000 8000 ...
Страница 8: ...Page vi IM02601004E www eaton ...
Страница 19: ...www eaton com IM02601004E Page 11 1 Introduction ...
Страница 24: ...Page 16 IM02601004E www eaton ...
Страница 36: ...Page 18 IM02601004E www eaton com 2 Quick Start Guide for the Meter Module ...
Страница 45: ...www eaton com IM02601004E Page 37 3 Installation 3 8 MeterDimensions ...
Страница 46: ...Page 38 IM02601004E www eaton 3 Installation Dimension Con t ...
Страница 47: ...www eaton com IM02601004E Page 39 3 Installation Dimension Con t ...
Страница 48: ...Page 40 IM02601004E www eaton 3 Installation Dimension Con t ...
Страница 53: ...www eaton com IM02601004E Page 45 3 Installation ...
Страница 54: ...Page 46 IM02601004E www eaton 3 Installation ...
Страница 55: ...www eaton com IM02601004E Page 47 3 Installation ...
Страница 56: ...Page 48 IM02601004E www eaton 3 Installation ...
Страница 57: ...www eaton com IM02601004E Page 49 3 Installation ...
Страница 58: ...Page 50 IM02601004E www eaton 3 Installation ...
Страница 59: ...www eaton com IM02601004E Page 51 3 Installation ...
Страница 60: ...Page 52 IM02601004E www eaton 3 Installation ...
Страница 61: ...www eaton com IM02601004E Page 53 3 Installation ...
Страница 62: ...Page 54 IM02601004E www eaton 3 Installation ...
Страница 63: ...www eaton com IM02601004E Page 55 3 Installation ...
Страница 66: ...Page 58 IM02601004E www eaton 3 Installation ...
Страница 75: ...www eaton com IM02601004E Page 67 4 Introduction to Web Server Screens ...
Страница 76: ...Page 68 IM02601004E www eaton 4 Introduction to Web Server Screens ...
Страница 86: ...Page 78 IM02601004E www eaton 5 Introduction to the Local Graphical Display ...
Страница 108: ...Page 100 IM02601004E www eaton 6 Functions on the Web Server Pages ...
Страница 128: ...Page 120 IM02601004E www eaton 7 Functions on the Graphical Display ...
Страница 164: ...Page 156 IM02601004E www eaton 8 Setup on the Web Server Pages ...
Страница 198: ...Page 190 IM02601004E www eaton A MODBUS Communication ...
Страница 242: ...Page 234 IM02601004E www eaton ...
Страница 252: ...Page 244 IM02601004E www eaton D Diagnostics ...
Страница 254: ...Page 246 IM02601004E www eaton D Diagnostics ...