20
XCHARGEIN MOBILITY INSTALLATION MANUAL
MN191005EN April 2021 www.eaton.com
00 Title
In case of three phases, connect the phase (L1, L2, L3), neutral (N) and earth (PE) wires of the AC terminals
to the GRID terminal block, respecting the correct assignment:
•
Phase (L1)
L1 terminal
•
Phase (L2)
L2 terminal
•
Phase (L3)
L3 terminal
•
Neutral (N)
N terminal
•
Earth (PE)
PE terminal
In case of a single phase, connect the phase (L1), neutral (N) and earth (PE) wires of the AC terminals to the
GRID terminal block, respecting the correct assignment:
•
Phase (L1)
L1 terminal
•
Neutral (N)
N terminal
•
Earth (PE)
PE terminal
Be careful not to reverse the phases with the neutral. If this happens, the system might malfunction.
Figure 14. How to wire AC grid connectors to the energy distribution board
It is prohibited to connect the unit terminals to a circuit with an IT grid configuration.
Three-phase terminals L1, L2, L3 and PE Single-phase terminals L1, N and PE