Panel Configuration
Silence Mode Disabled
With switch 3 of SW12 on the panel main board set to
Silence
Mode Disabled
the panel will re-sound all fire alarm devices after
the panel has been silenced with any new fire conditions detected
(see Figure 27) .
Silence Mode Enabled
With switch 3 of SW12 on the panel main board set to
Silence
Mode Enabled
the panel will NOT re-sound the fire alarm devices
after the panel has been silenced regardless of any new fire condi-
tions detected .
Zone Configuration
Set each zone to Normal (standard conventional) or Intrinsically
Safe mode at SW3 (see Figure 28 and the accompanying table) .
Zone #
Standard Conventional
Intrinsically Safe Conventional
1
SW3 .1 = OFF
SW3 .1 = ON
2
SW3 .2 = OFF
SW3 .2 = ON
3
SW3 .3 = OFF
SW3 .3 = ON
4
SW3 .4 = OFF
SW3 .4 = ON
5
SW3 .5 = OFF
SW3 .5 = ON
6
SW3 .6 = OFF
SW3 .6 = ON
7
SW3 .7 = OFF
SW3 .7 = ON
8
SW3 .8 = OFF
SW3 .8 = ON
Detector Fitting
All detector heads should now be fitted to the bases (following the
device installation guide), prior to the installation being tested .
If there are no detectors or manual call points showing the fire
condition then the zone can be re-enabled at the panel .
If there are no detectors or manual call points showing the fire
condition then the zone can be re-enabled at the panel .
WARNING
FAILURE TO FOLLOW THE INSTRUCTIONS ABOVE
WILL RESULT IN THE PANEL ENTERING A FULL ALARM
CONDITION WHICH WILL EVACUATE THE SITE AND
ACTIVATE ANY OTHER EQUIPMENT ATTACHED TO THE
FIRE ALARM SYSTEM.
Figure 27. Silence Mode setting
Figure 28. Zone configuration setting