Individual Zone Test
This function is only available at access level 2 .
This function will allow individual zones to be placed in the zone
test mode .
•
Enter the access code 3112
•
Press
Test
button
②
.
•
The zone currently in test mode will have its associated
disabled indicator lit and all zones not in test mode will have
their associated disabled indicators unlit .
•
The function always starts at Zone 1 .
•
When an item is selected for test mode its disable indicator will
change from unlit to lit .
•
When an item is selected for normal operation its disable indi-
cator will change from lit to unlit .
•
Press the following button sequences for the required test
mode/normal operation:
Item
2-Zone
4-Zone
8-Zone
Zone 1
3
3
3
Zone 2
2 + 3
2 + 3
2 + 3
Zone 3
2 (2 times) + 3
2 (2 times) + 3
Zone 4
2 (3 times) + 3
2 (3 times) + 3
Zone 5
2 (4 times) + 3
Zone 6
2 (5 times) + 3
Zone 7
2 (6 times) + 3
Zone 8
2 (7 times) + 3
•
Pressing
Select
button
③
will accept the selected test zone
and exit back to Access Level 1 . The Test indicator will remain lit
and the zone disabled indicator will also remain lit .
•
When a fire detection device or manual call point is activated
in the zone under test it will sound all fire alarm devices for 3
seconds and then will automatically silence .
•
Any fire condition detected in any other zone will place the
system into full alarm condition and the fire alarm devices will
activate continuously .
•
To end the individual test mode the above selection instructions
should be carried out and the zone disabled indicator changed
to the unlit state .
Lamp Test
This function is available at access level 2 .
•
Enter the access code 3112 .
•
Press
Indicator Test
button
③
.
•
Each indicator on the front of the panel will turn on in turn and
then turn off in turn (excluding the Power On indicator) .
This function will immediately exit back to Access Level 1 .