Installation and operation manual for
conventional fire panels
EATON
www.eaton.com
Operating Instructions
Multi-Function Buttons
The numerical value in the centre of the button is used to enter
access codes for level 2 and 3 .
If the text in the centre of the button appears above a line (or
there is no line) then this function is applicable at access level 2 . If
the text in the centre of the button appears below a line then this
function is applicable at access level 3 .
The text above button 3 indicates that this button is the
Select
button during the
Disable/Enable
and
Individual Zone Test
functions .
Silence Fire Alarm Devices
This function is only available at access level 2 and when the
alarms are sounding .
• Enter the access code 3112 .
• Press the
Silence/Sound Alarms
button .
• Only the fire alarm devices will stop sounding, the panel buzzer
will continue sounding .
• This function will immediately exit back to Access Level 1 .
Sound Fire Alarm Devices
This function is only available at access level 2 and when the
alarms are silent .
• Enter the access code 3112 .
• Press the
Silence/Sound Alarms
button .
• Only the General Fire indicator will be lit, the panel buzzer will
sound a continuous tone and all fire alarm devices will sound .
• This function will immediately exit back to Access Level 1 .
Reset System
This function is only available at access level 2 .
•
Enter the access code 3112 .
•
Press the
Reset
button .
•
This will stop all fire alarm devices sounding, will stop the panel
buzzer and will reset the panel .
•
The panel will return to the normal condition after completing
the indicator test routine which turns each indicator on in turn
and then turns them off in turn .
NOTE
WHEN PERFORMING A RESET, ANY TEST CASES WILL BE
CLEARED.