Installation and operation manual for  

conventional fire panels 

  

EATON

 www.eaton.com

Operating Instructions

Multi-Function Buttons

The numerical value in the centre of the button is used to enter 

access codes for level 2 and 3 .
If the text in the centre of the button appears above a line (or 

there is no line) then this function is applicable at access level 2 . If 

the text in the centre of the button appears below a line then this 

function is applicable at access level 3 .
The text above button 3 indicates that this button is the 

Select

 

button during the 

Disable/Enable

 and 

Individual  Zone Test

 

functions .

Silence Fire Alarm Devices

This function is only available at access level 2 and when the 

alarms are sounding .
• Enter the access code 3112 .
• Press the 

Silence/Sound Alarms

 button .

• Only the fire alarm devices will stop sounding, the panel buzzer

will continue sounding .
• This function will immediately exit back to Access Level 1 .

Sound Fire Alarm Devices

 This function is only available at access level 2 and when the 

alarms are silent .
• Enter the access code 3112 .
• Press the 

Silence/Sound Alarms

 button .

• Only the General Fire indicator will be lit, the panel buzzer will

sound a continuous tone and all fire alarm devices will sound .
• This function will immediately exit back to Access Level 1 .

Reset System

This function is only available at access level 2 .

Enter the access code 3112 .

Press the 

Reset

 button .

This will stop all fire alarm devices sounding, will stop the panel

buzzer and will reset the panel .

The panel will return to the normal condition after completing

the indicator test routine which turns each indicator on in turn

and then turns them off in turn .

  NOTE

WHEN PERFORMING A RESET, ANY TEST CASES WILL BE 

CLEARED.

Technical Data 

25-16733-A

Effective 

October 2019

Содержание EFCV2Z

Страница 1: ...Conventional Fire Panels Installation and operation manual EFCV2Z EFCV4Z EFCV8Z EFCV2Z NB EFCV4Z NB EFCV8Z NB October 2019...

Страница 2: ...ing the Battery Supply 15 Battery Connections 16 Connecting the Input Output Cables 17 Interlinking Two Panels 17 Option Board 18 Panel Configuration 19 Zone Configuration 19 Detector Fitting 19 Insta...

Страница 3: ...call points on the zone along with an intrinsi cally safe barrier The Eaton Conventional re alarm system is certi ed to EN54 part 2 and part 4 and is designed to meet the recommendations in BS5839 The...

Страница 4: ...remaining zones will continue to monitor for secondary res or fault conditions The panel also continuously monitors the state of each conven tional sounder circuit and will report any fault condition...

Страница 5: ...is provided in the PSE Specification on page 28 Note that the charging circuit will be in its high impedance state approximately 3V DC if no batteries faulty batteries or only one battery is connected...

Страница 6: ...ection detectors and call points devices only and must be terminated with an EOLM 1 embedded in the last device Figure 4 Intrinsically safe conventional detection devices cannot be wired onto a conven...

Страница 7: ...LOW No battery voltage or battery voltage too low Mains Fault ON ON ON SLOW Mains voltage has been lost Battery Failure ON ON SLOW SLOW Battery impedance fault Charger Fault ON ON ON SLOW Charger volt...

Страница 8: ...put must be considered when calculating battery standby times The contacts are not monitored Class Change The sounders can be operated by an external volt free contact Figure 8 A short circuit at this...

Страница 9: ...peater fault FRE fault FPE fault Interlink Relay The Interlink Relay in conjunction with a non latching zone can be used to link two EFCV fire panels together Figure 10 It is recom mended to use a non...

Страница 10: ...te during a fire event and is connected to phone diallers and or Building Management Systems When the FRE option board is fitted SW12 1 dip switch is set to Fitted See Battery Connections on page 16 T...

Страница 11: ...SULT IN DAMAGE TO THE EQUIPMENT AND COULD INVALIDATE YOUR WARRANTY Figure 12 System Cabling NOTE WHEN INSTALLED THIS EQUIPMENT IS SUBJECT TO THE EMC DIRECTIVE 2004 108 EC TO MAINTAIN EMC COMPLIANCE TH...

Страница 12: ...TENTIAL HAZARD IN A POSITION WHERE IT IS READILY ACCESSIBLE TO AUTHORISED STAFF AND THE FIRE SERVICES IDEALLY ON THE PERIMETER OF A BUILDING NEAR A PERMANENT ENTRANCE Mounting the Panel To prepare the...

Страница 13: ...emove the screw and push the PCB up to the right and forwards as shown in Figure 16 Once the cable entry holes have been cut then fit the cable glands to the back box If the panel is being flush mount...

Страница 14: ...into the wall and insert wall plugs and secure the panel to the wall as shown in Figure 18 Ensure any dust is cleaned from the back box Secure the PSE PCB back into the back box by following the reve...

Страница 15: ...VOLT DROP LIMITATION WHEN SIZING CABLES USE ONLY APPROVED CABLE TYPES DO NOT TIGHTEN TERMINAL CONNECTOR SCREWS TOO TIGHT KEEP POLARITY THROUGHOUT NON COLOURED CONDUCTORS SHOULD BE PERMANENTLY MARKED...

Страница 16: ...cables clearly labelled with the zone numbers to the appropriate zone terminals observing the correct polarity see Figure 22 If any of the zones are not used then the EOLM 1 must remain fitted to the...

Страница 17: ...e panel main board must be changed to the Repeater Output On setting see Figure 23 Interlinking Two Panels Wire the two panels together as shown in Figure 25 The EOLM 1 must be fitted for the zone cir...

Страница 18: ...L ON THE OPTION BOARD THIS PREVENTS ERRONEOUS FAULT CONDITIONS BEING DISPLAYED ON THE PANEL Connecting the Zonal Outputs Connect the cabling from the external equipment to the relevant zone terminals...

Страница 19: ...onventional Intrinsically Safe Conventional 1 SW3 1 OFF SW3 1 ON 2 SW3 2 OFF SW3 2 ON 3 SW3 3 OFF SW3 3 ON 4 SW3 4 OFF SW3 4 ON 5 SW3 5 OFF SW3 5 ON 6 SW3 6 OFF SW3 6 ON 7 SW3 7 OFF SW3 7 ON 8 SW3 8 O...

Страница 20: ...panel to clear the fire condition before you re enable the zone Check that the following outputs are in the correct state Auxillary Output 30V Fire Relay C NC Fault Relay C NO Interlink Relay C NC FRE...

Страница 21: ...ts Battery Check WARNING THIS TEST WILL ACTIVATE ANY EXTERNAL EQUIPMENT CONNECTED TO THE FRE FPE OR FIRE RELAYS IF THE ACTIVATION OF THE EQUIPMENT IS NOT DESIRED THEN THE EQUIPMENT MUST BE DISABLED DI...

Страница 22: ...o be conducted by the Premises Management Each week perform a Lamp Test to check that all visual and audible indicators on the panel are functioning correctly See LampTest on page 25 Each week a diffe...

Страница 23: ...y the fire alarm devices will stop sounding the panel buzzer will continue sounding This function will immediately exit back to Access Level 1 Sound Fire Alarm Devices This function is only available...

Страница 24: ...ite and activate any other equipment attached to the fire alarm system This function will allow the following to be disabled Individual Zones All fire alarm devices FRE if fitted FPE if fitted Enter t...

Страница 25: ...mes 3 Zone 5 2 4 times 3 Zone 6 2 5 times 3 Zone 7 2 6 times 3 Zone 8 2 7 times 3 Pressing Select button will accept the selected test zone and exit back to Access Level 1 The Test indicator will rema...

Страница 26: ...he Test indicator will turn on and the buzzer will give a slow pulsing tone This function places all zones in test mode and is used during commissioning to test every fire detection device on a zone R...

Страница 27: ...r of sounder outputs 2 2 4 Maximum loading per output 250mA Fuse protection per output 250mA PTC End of Line Termination per output 6K8 resistor Unmonitored Outputs Fire Relay Type Volt Free Single Po...

Страница 28: ...atteries 2 Capacity 12V 5Ah Recommended Battery Yucell Y5 12 Yuasa NPH5 12 Battery Fuse 6 3A Anti Surge Battery voltage Charging value 27 3V DC 20 Recommended period for battery replacement 5 years Ba...

Страница 29: ...PE Output Rating 24V 50mA Fuse 50mA PTC EOLR 6 8K Number of Auxiliary Relays 2 4 8 Auxiliary Relays Un monitored Type Volt Free Single Pole Double Throw Rating 30V DC 50mA Fuse 500mA PTC Cable Specifi...

Страница 30: ...Intended for the use in fire detection and fire alarm systems in and around buildings EN54 4 EFCV2ZONE EFCV4ZONE EFCV8ZONE Intended for the use in fire detection and fire alarm systems in and around...

Страница 31: ...31 Installation and operation manual for conventional fire panels EATON www eaton com Technical Data 25 16733 A Effective October 2019...

Страница 32: ...1110 Morges Switzerland Eaton eu TEL 44 0 1302 321541 FAX 44 0 1302 303220 Firesales eaton com Firetechsupport eaton com Eaton Electrical Systems Ltd Wheatley Hall Road Doncaster DN2 4NB TEL 44 0 1302...

Отзывы: