background image

10

Installation and operation manual for  

conventional fire panels 

EATON

 www.eaton.com

1 2

1 2

1 2

Technical Data 

25-

16733

-A

 

Effective 

October 2019

Detector Zone Inputs

Each zone is configured by default to Conventional mode and is 

provided with an EOLM-1 fitted inside the panel . For zones that 

need to be in Standard Conventional mode the EOLM-1 must be 

removed from the panel and fitted to the last device on each zone . 

Any unused zones must be terminated inside the panel by the 

EOLM-1 otherwise the zone will go into fault condition .
For zones to be configured in Intrinsically Safe Conventional mode 

the EOLM-1 must be removed and replaced by a 5K1 resistor (not 

supplied) and fitted in the last device at the end of zone after the 

intrinsically safe barrier . Any unused intrinsically safe zones must 

be terminated by the 5K1 end-of-line resistor .
It is recommended that any zone that is not in use should remain 

in the factory default configuration of Standard Conventional mode 

with the EOLM-1 fitted in the panel .

Repeater I/O

The Fire Panel provides a monitored RS485 bus that allows for up 

to 3 passive repeater panels to be connected to it .  The repeater 

panels have their own power supplies so no power connection 

is required from the Fire Panel . Each repeater panel must be 

assigned a unique address using the DIP switches provided on the 

repeaters (see repeater manual for details) .
On power-up or after a hard reset the Fire Panel will perform it’s 

lamp test .  Once this is complete the Fire Panel will scan the 

RS485 bus for any repeaters connected .  The panel will briefly 

flash the Zone Fault indicators to show the number of repeaters it 

has found .  Below is a table of what these indications mean .

It is important to note this during installation to ensure that the 

panel has found the correct number of repeaters .
Once the repeaters have been found the Fire Panel will broadcast 

all status information to them so that they will mirror the indicator 

and buzzer states of the Fire Panel .  The Fire Panel expects to 

receive a response from each repeater, if at any time a repeater 

stops responding for more than 60 seconds then the Fire Panel 

will start to flash the “Repeater Fault” indicator .

Option Board (FRE/FPE/Zonal Relays)

 

The options board is an additional daughter card that provides 

outputs to Fire Protection Equipment (FPE), Fire Alarm Routing 

Equipment (FRE) and Zonal Relays .

 

Fire Alarm Routing Equipment (FRE)

 

The FRE output is designed to activate during a fire event and 

is connected to phone diallers and/or Building Management 

Systems . When the FRE option board is fitted SW12-1 dip switch 

is set to Fitted . See 

Battery Connections on page 16

 . The 

output complies with EN54-2 clause:

7 .9 .1 Outputs to fire alarm routing equipment (option with

requirements)

Fire Protection Equipment (FPE)

The FPE output is designed to activate during a fire event and 

when connected to external devices drive door release mecha-

nisms, fire screens, sprinkler systems, and gas release systems . 

When FPE option board fitted SW12-1 dip switch is set to Fitted . 

The output complies with EN54-2 clause:

7 .10 .1 Outputs to fire protection equipment (Type A)

Zonal Relay Contacts

Zonal relay contacts are volt free and do not provide any voltage . 

The relays are selectable to be either set to C/NO or C/NC . The 

zonal relays are designed to follow the fire condition of the associ-

ated zone circuit on the Main board . 

1 2

= 0 repeaters found 

= 1 repeater found 

= 2 repeaters found 

= 3 repeaters found 

Figure 11. Repeater Panel connection 

Содержание EFCV2Z

Страница 1: ...Conventional Fire Panels Installation and operation manual EFCV2Z EFCV4Z EFCV8Z EFCV2Z NB EFCV4Z NB EFCV8Z NB October 2019...

Страница 2: ...ing the Battery Supply 15 Battery Connections 16 Connecting the Input Output Cables 17 Interlinking Two Panels 17 Option Board 18 Panel Configuration 19 Zone Configuration 19 Detector Fitting 19 Insta...

Страница 3: ...call points on the zone along with an intrinsi cally safe barrier The Eaton Conventional re alarm system is certi ed to EN54 part 2 and part 4 and is designed to meet the recommendations in BS5839 The...

Страница 4: ...remaining zones will continue to monitor for secondary res or fault conditions The panel also continuously monitors the state of each conven tional sounder circuit and will report any fault condition...

Страница 5: ...is provided in the PSE Specification on page 28 Note that the charging circuit will be in its high impedance state approximately 3V DC if no batteries faulty batteries or only one battery is connected...

Страница 6: ...ection detectors and call points devices only and must be terminated with an EOLM 1 embedded in the last device Figure 4 Intrinsically safe conventional detection devices cannot be wired onto a conven...

Страница 7: ...LOW No battery voltage or battery voltage too low Mains Fault ON ON ON SLOW Mains voltage has been lost Battery Failure ON ON SLOW SLOW Battery impedance fault Charger Fault ON ON ON SLOW Charger volt...

Страница 8: ...put must be considered when calculating battery standby times The contacts are not monitored Class Change The sounders can be operated by an external volt free contact Figure 8 A short circuit at this...

Страница 9: ...peater fault FRE fault FPE fault Interlink Relay The Interlink Relay in conjunction with a non latching zone can be used to link two EFCV fire panels together Figure 10 It is recom mended to use a non...

Страница 10: ...te during a fire event and is connected to phone diallers and or Building Management Systems When the FRE option board is fitted SW12 1 dip switch is set to Fitted See Battery Connections on page 16 T...

Страница 11: ...SULT IN DAMAGE TO THE EQUIPMENT AND COULD INVALIDATE YOUR WARRANTY Figure 12 System Cabling NOTE WHEN INSTALLED THIS EQUIPMENT IS SUBJECT TO THE EMC DIRECTIVE 2004 108 EC TO MAINTAIN EMC COMPLIANCE TH...

Страница 12: ...TENTIAL HAZARD IN A POSITION WHERE IT IS READILY ACCESSIBLE TO AUTHORISED STAFF AND THE FIRE SERVICES IDEALLY ON THE PERIMETER OF A BUILDING NEAR A PERMANENT ENTRANCE Mounting the Panel To prepare the...

Страница 13: ...emove the screw and push the PCB up to the right and forwards as shown in Figure 16 Once the cable entry holes have been cut then fit the cable glands to the back box If the panel is being flush mount...

Страница 14: ...into the wall and insert wall plugs and secure the panel to the wall as shown in Figure 18 Ensure any dust is cleaned from the back box Secure the PSE PCB back into the back box by following the reve...

Страница 15: ...VOLT DROP LIMITATION WHEN SIZING CABLES USE ONLY APPROVED CABLE TYPES DO NOT TIGHTEN TERMINAL CONNECTOR SCREWS TOO TIGHT KEEP POLARITY THROUGHOUT NON COLOURED CONDUCTORS SHOULD BE PERMANENTLY MARKED...

Страница 16: ...cables clearly labelled with the zone numbers to the appropriate zone terminals observing the correct polarity see Figure 22 If any of the zones are not used then the EOLM 1 must remain fitted to the...

Страница 17: ...e panel main board must be changed to the Repeater Output On setting see Figure 23 Interlinking Two Panels Wire the two panels together as shown in Figure 25 The EOLM 1 must be fitted for the zone cir...

Страница 18: ...L ON THE OPTION BOARD THIS PREVENTS ERRONEOUS FAULT CONDITIONS BEING DISPLAYED ON THE PANEL Connecting the Zonal Outputs Connect the cabling from the external equipment to the relevant zone terminals...

Страница 19: ...onventional Intrinsically Safe Conventional 1 SW3 1 OFF SW3 1 ON 2 SW3 2 OFF SW3 2 ON 3 SW3 3 OFF SW3 3 ON 4 SW3 4 OFF SW3 4 ON 5 SW3 5 OFF SW3 5 ON 6 SW3 6 OFF SW3 6 ON 7 SW3 7 OFF SW3 7 ON 8 SW3 8 O...

Страница 20: ...panel to clear the fire condition before you re enable the zone Check that the following outputs are in the correct state Auxillary Output 30V Fire Relay C NC Fault Relay C NO Interlink Relay C NC FRE...

Страница 21: ...ts Battery Check WARNING THIS TEST WILL ACTIVATE ANY EXTERNAL EQUIPMENT CONNECTED TO THE FRE FPE OR FIRE RELAYS IF THE ACTIVATION OF THE EQUIPMENT IS NOT DESIRED THEN THE EQUIPMENT MUST BE DISABLED DI...

Страница 22: ...o be conducted by the Premises Management Each week perform a Lamp Test to check that all visual and audible indicators on the panel are functioning correctly See LampTest on page 25 Each week a diffe...

Страница 23: ...y the fire alarm devices will stop sounding the panel buzzer will continue sounding This function will immediately exit back to Access Level 1 Sound Fire Alarm Devices This function is only available...

Страница 24: ...ite and activate any other equipment attached to the fire alarm system This function will allow the following to be disabled Individual Zones All fire alarm devices FRE if fitted FPE if fitted Enter t...

Страница 25: ...mes 3 Zone 5 2 4 times 3 Zone 6 2 5 times 3 Zone 7 2 6 times 3 Zone 8 2 7 times 3 Pressing Select button will accept the selected test zone and exit back to Access Level 1 The Test indicator will rema...

Страница 26: ...he Test indicator will turn on and the buzzer will give a slow pulsing tone This function places all zones in test mode and is used during commissioning to test every fire detection device on a zone R...

Страница 27: ...r of sounder outputs 2 2 4 Maximum loading per output 250mA Fuse protection per output 250mA PTC End of Line Termination per output 6K8 resistor Unmonitored Outputs Fire Relay Type Volt Free Single Po...

Страница 28: ...atteries 2 Capacity 12V 5Ah Recommended Battery Yucell Y5 12 Yuasa NPH5 12 Battery Fuse 6 3A Anti Surge Battery voltage Charging value 27 3V DC 20 Recommended period for battery replacement 5 years Ba...

Страница 29: ...PE Output Rating 24V 50mA Fuse 50mA PTC EOLR 6 8K Number of Auxiliary Relays 2 4 8 Auxiliary Relays Un monitored Type Volt Free Single Pole Double Throw Rating 30V DC 50mA Fuse 500mA PTC Cable Specifi...

Страница 30: ...Intended for the use in fire detection and fire alarm systems in and around buildings EN54 4 EFCV2ZONE EFCV4ZONE EFCV8ZONE Intended for the use in fire detection and fire alarm systems in and around...

Страница 31: ...31 Installation and operation manual for conventional fire panels EATON www eaton com Technical Data 25 16733 A Effective October 2019...

Страница 32: ...1110 Morges Switzerland Eaton eu TEL 44 0 1302 321541 FAX 44 0 1302 303220 Firesales eaton com Firetechsupport eaton com Eaton Electrical Systems Ltd Wheatley Hall Road Doncaster DN2 4NB TEL 44 0 1302...

Отзывы: