Technical Specifications
Panel Specification
EFCV2ZONE
EFCV4ZONE
EFCV8ZONE
Power Specification
Input Voltage Range
18 .75-30 .7V DC
Maximum current drawn from battery
2 .7A
Zone Circuits
Number of Zones
2
4
8
Devices per Zone
Standard
Conventional Mode:
Max 32 Detectors and Manual Call Points
Intrinsically Safe Mode:
Max of 10 Intrinsically Safe Detectors and Manual Call Points
Maximum loading per Zone
200mA
Standby Zone Voltage
Vmin
19V DC
Vmax
23V DC
Alarm Zone Voltage
Vmin
19V DC
Vmax
23V DC
Alarm Resistance
(Conventional Mode)
Rmin
100Ω
Rmax
750Ω
Fuse Protection Per Zone
250mA PTC
End of Line Termination
Standard Conventional Zones:
EOLM-1 only
Intrinsically Safe Zones:
6K8 resistor
WARNING: YOU MUST USE THE CORRECT END OF LINE TERMINATION
Conventional Sounder Outputs
Number of sounder outputs
2
2
4
Maximum loading per output
250mA
Fuse protection per output
250mA PTC
End of Line Termination per output
6K8 resistor
Unmonitored Outputs
Fire Relay
Type
Volt-Free, Single Pole Double Throw
Rating
30V DC, 1A
Fuse
500 mA PTC
Fault Relay
Type
Volt-Free, Single Pole Double Throw
Rating
30V DC 1A
Fuse
500mA PTC
Interlink Relay
Type
Volt-Free, Single Pole Double Throw
Rating
30V DC, 1A
Fuse
500mA PTC
Auxiliary Output
V
18 .15V - 30 .7V DC
Imax
50 mA
Fuse
50mA PTC
Intrinsically Safe Barrier
A
MTL5561 (Dual Channel, can take 2 zones per barrier)
B
MTL7778AC (Single Channel)
Unmonitored Inputs
Class Change
Type
Open Circuit: Normal Panel Operation
Short Circuit: Activate all Sounders
Communication Ports
Repeater Port
Type
RS485
Nodes
3
Note:
The use of this port is outside the scope of EN54 certification
Environmental
Operating Temperature
°
C
-5
°
C to +40
°
C
Relative Humidity
%
93% +/3% non-condensing
IP Rating
IP30
Mechanical
Dimensions
mm
375 (W) x 366 (H) x 134 (D)
Weight
Kg
2 .25
Material
PC ABS Front and Rear
Technical Data
25-16733-A
Effective
October 2019