Connecting the FRE and FPE Outputs
Connect the cabling from the fire alarm routing equipment and
fire protection equipment to the relevant terminals on the option
board (see Figure 26) .
As these outputs are monitored for short circuit and open circuit
faults conditions, the 6K8 resistor supplied should be installed at
the external equipment and not at the option board terminals .
Figure 26. Option board wiring diagram
NOTE
IF EITHER THE FRE OR FPE IS NOT BEING USED THEN THE
6K8 RESISTOR SHOULD BE FITTED AT THE APPROPRIATE
TERMINAL ON THE OPTION BOARD. THIS PREVENTS
ERRONEOUS FAULT CONDITIONS BEING DISPLAYED ON THE
PANEL.
Connecting the Zonal Outputs
Connect the cabling from the external equipment to the relevant
zone terminals on the option board .
These outputs are not monitored so there is no need for a 6K8
termination resistor .
Change the jumpers on the zonal relays to get them to operate
in either normally open or normally closed during a fire alarm
condition .