3. Installation
3.6 Preparing the device for operation
WARNING
RTD units are products designed for use in industrial environments
as defined in ICE/EN 6100−6-4. These products can cause radio inter-
ference in domestic environments. In this case, the party operating
the products must implement appropriate radio interference sup-
pression measures.
CAUTION
Installation requires qualified electrician
Arrange for an electrician to install and connect the power supply.
3.6.1 Power supply – electrical connection
The RTD features an internal fuse and protection against polarity reversal. The hous-
ing is made of plastic and serves as an insulator.
The power supply for the device is
not
galvanically isolated.
The RTD requires a rated operating voltage of 24 V
DC
from a DC-to-DC converter
with safe isolation (SELV/PELV).
Rated operating voltage
24 V DC (-20%/+25%)
Permissible voltage range
Effective: 19.2-30.0 V DC (rated operating voltage -20%/+25%)
Absolute with ripple: 18.0-31.2 V DC
Battery powered: 18.0-31.2 V DC (rated operating voltage -25%/+30%)
Power consumption
max. 7.2 W
Current consumption at 24 V DC: 4.7 W for basic 2.5 W for USB mod-
ule
Fuse
Yes (fuse not accessible)
Potential isolation
no
Electrical current
Ie
≦ 0.3 A
I
TH
2.5 A²s
The required MC 1.5/ 2-ST-3.5 BK connector is included as standard.
signal
Configuration
+ 24VDC
Power supply
+ 24 VDC SELV (safety extra low voltage)/PELV (protective extra low voltage)
0V
0 V power supply
Tab. 3: Plug connection configuration MC 1.5/ 2-ST-3.5 BK
easyE Remote Touch Display
01/24 MN048027EN Eaton.com
47
Содержание easyE
Страница 1: ...Manual 01 24 MN048027EN easyE Remote Touch DisplayManual...
Страница 4: ......
Страница 8: ...8 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Страница 14: ...0 1 About this documentation 14 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Страница 26: ...1 Description 1 10 Marine approvals 26 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Страница 34: ...2 Safety regulations 2 3 Device specific hazards 34 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Страница 50: ...3 Installation 3 6 Preparing the device for operation 50 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Страница 54: ...4 External connections 4 2 Ethernet 54 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Страница 60: ...5 Commissioning 5 2 Initial commissioning 60 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Страница 88: ...7 Operation 7 2 Device menus 88 easyE Remote Touch Display 01 24 MN048027EN Eaton com...
Страница 108: ...Appendix A 2 Further usage information 108 easyE Remote Touch Display 01 24 MN048027EN Eaton com...