Instruction Leaflet 

I. L. 29-889B

Effective June 2011

 Instructions for Digitrip RMS 910 Trip Unit

 

 

eaton corporation

 www.eaton.com

is reset (see Section 5 .9) .  The Trip Unit displays "EXTT" in its window 

and sends back the "EXTT message over INCOM to the remote 

master computer .  (Note that the values of the currents through the 

circuit breaker will be "zero" when it is OPEN .)

WARNING

UNEXPECTED SIGNALS TO "CLOSE' OR "TRIP' A CIRCUIT BREAKER FROM 

A REMOTE LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE 

PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE 

IMMEDIATE VICINITY OF THE CIRCUIT BREAKER.  PROVIDE PERMISSIVE 

CONTROL SWITCHES, OR OTHER MEANS, LOCALLY AT THE CIRCUIT 

BREAKER FOR MAINTENANCE PERSONNEL TO USE IN CONTROLLING 

REMOTE "CLOSE" OR "TRIP" SIGNALS.  FOR DETAILED INFORMATION 

CONCERNING THE BREAKER CONTROL CIRCUITS NECESSARY TO 

IMPLEMENT PERMISSIVE CONTROL LOCALLY, REFER TO THE CIRCUIT 

BREAKER CONNECTION DIAGRAMS LISTED IN SECTION 6.

5.9  Remote Resetting of the Trip Unit

NOTICE

BEFORE RESETTING TRIP UNIT, BE SURE TO: 

  • RECORD DISPLAY VALUES OF ALL PERTINENT PARAMETERS. 

  • NOTE WHICH CAUSE OF TRIP LEDS ARE LIGHTED "RED”. 

  • CORRECT THE CAUSE OF THE OVERCURRENT OR FAULT CONDITION  

     THAT CAUSED THE BREAKER TO TRIP. 

 

BECAUSE THE AUTOMATIC LOCKOUT-AFTER-TRIP FEATURE OF THE 

DIGITRIP RMS 910 TRIP UNIT MAINTAINS THE CIRCUIT BREAKER IN A 

"TRIP-FREE" CONDITION.  THE TRIP UNIT MUST BE RESET AFTER EACH 

TRIP OPERATION (WHETHER INITIATED BY OVER-CURRENT CONDITIONS 

OR BY REMOTE INCOM

®

 / IMPACC

®

 SIGNAL), BEFORE THE BREAKER CAN 

BE CLOSED AGAIN.  THE RESET CAN BE ACCOMPLISHED EITHER LOCALLY 

BY PRESSING AND RELEASING THE "TRIP RESET" PUSH BUTTON (SEE 

FIGURE 1), OR REMOTELY BY THE IMPACC

®

 SYSTEM.

Although the reset can be accomplished locally by pressing and 

releasing the "TRIP RESET push button (see Figure 1), it is some-

times inconvenient or untimely to go to the circuit breaker in order 

to reset the Trip Unit .  For such cases where the circuit breaker is 

far from the plant control room, the IMPACC

®

 system provides the 

User with a means for resetting the circuit breaker through the com-

munications network "Trip Unit Reset" command .  Executing the Trip 

Unit Reset command remotely from the master computer by the 

INCOM

®

 / lMPACC

®

 system is exactly equivalent to pressing and 

releasing the "Trip Reset" push-button on the front of the Trip Unit .
In addition to the Trip Unit Reset capability, the INCOM

®

 / IMPACC

®

 

communications capability of the Trip Unit provides the User with a 

means for resetting several parameter values stored in the Trip Unit's 

memory .  Using the proper commands, the User can view and reset 

the following trip event buffer parameters remotely: time of trip, val-

ues of phase and ground currents, number of electronically initiated 

trip operations, peak [power] demand, energy, and the cause of trip .

6  references

6.1  Digitrip RMS Trip Assemblies

I .L . 29-885 

lnstructions for Digitrip RMS 510 Trip Unit

I .L . 29-886 

lnstructions for Digitrip RMS 610 Trip Unit

I .L . 29-888 

lnstructions for Digitrip RMS 810 Trip Unit

I .L . 29-889 

lnstructions for Digitrip RMS 910 Trip Unit

6.2  Type DS Low-Voltage AC Power Circuit Breakers

I .B . 33-790-1 

lnstructions for Low Voltage Power Circuit  

 

 

Breakers Types DS and DSL

Supplement B       Digitrip RMS 510, 610, and 910 Trip Units with 

to I .B . 32-790-1 

Types DS and DSL Low Voltage Power Circuit  

 

 

Breakers

AD 32-870 

Typical Time-Current Characteristic Curves for  

 

 

Types DS and DSL Circuit Breakers

SC-5619 

Instantaneous (I)

SC-5620 

Long Delay and Short Delay (LS)

SC-5621 

Ground (G)

508B508  

Connection Diagram for Type DS Circuit Breakers

6.3  Type DS II Low-Voltage AC Power Circuit Breakers

I .B . 694C694 

Instructions for Low-Voltage Power Circuit  

 

 

Breakers Types DS ll and DSL ll

Supplemental  

Digitrip RMS and Optim Trip Units with Type DS ll 

I .L . 8700C39 

and DSL ll Low-Voltage AC Power Circuit Breakers

AD 32-870 

Typical Time-Current Characteristic Curves for  

 

 

Types DS ll and DSL ll Circuit Breakers

SC-5619  

Instantaneous (I)

SC-5620  

Long Delay and Short Delay (LS)

SC-5621  

Ground (G)

1A33600  

Connection Diagram for Type DS ll Circuit  

 

 

Breakers

6.4  Type SPB Systems Pow-R

I .L . 29-801 

lnstruction for the Systems Pow-R Breaker and  

 

 

Drawout Mechanism

I .L . 29-849 

Supplementary lnstructions for the Systems  

 

 

Pow-R Breaker used with the Digitrip RMS Trip  

 

 

Units

AD 29-863 

Typical Time-Current Characteristic Curves for 

 

 

 Type SPB Systems Pow-R Breaker

SC-5623 

lnstantaneous (I)

SC-5624 

Long Delay and Short Delay (LS)

SC-5625 

Ground (G)

I .S . 15545 

SPB Master Connection Diagram

Содержание Digitrip RMS 910

Страница 1: ...Effective June 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 889B Instructions for Digitrip RMS 910 Trip Unit...

Страница 2: ...3 4 Short Delay Current Setting 18 3 5 Short Delay Time Setting 18 3 6 Instantaneous Current Setting 18 3 7 No Instantaneous Current Setting 19 3 8 Ground Fault Current Setting 19 3 9 Ground Fault Tim...

Страница 3: ...Figure 15 Short Delay Current Settings 16 Figure 16 Short Delay Time Settings 17 Figure 17 Instantaneous Current Settings 17 Figure 18 Ground Fault Current Settings 17 Figure 19 Ground Fault Time Dela...

Страница 4: ...urrent rating of each circuit breaker The Digitrip RMS 910 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 18...

Страница 5: ...on 1 4 will maintain the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 910 Trip Unit can be RESET in two ways Either pres...

Страница 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 9...

Страница 7: ...n Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp...

Страница 8: ...Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 910 Type Ll Figure 4 Digitrip RMS 910 Type LS Figure 5 Digitrip RMS 910 Type LSI F...

Страница 9: ...The non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approxi mately ten 10 cycles following the initial current flow through...

Страница 10: ...ppendix A 1 2 Four Character Information Display Window The four digit alpha numeric display window illustrated in Figures 1 and 2 serves two basic purposes instrumentation and mode of trip and troubl...

Страница 11: ...wer Power Factor and Energy Values 1 2 1 3 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X Power Factor X X X X X X 1 2 1 3 Energy Consumption MWh Rev...

Страница 12: ...lug is missing damaged or not well connected If breaker is closed it will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Pr...

Страница 13: ...l in Figure 1 Note N The peak demand function requires that 120 VAC control power be sup plied to the Power 1 Relay Module The Present Demand is a power value averaged over approximately one second To...

Страница 14: ...elease of the Step push button will initiate a 3 phase waveform capture internally in the Digitrip and in turn calculate all THD and individual values Notice that two Green LEDs THD and IA are now ill...

Страница 15: ...D OR FAILURE OF THE PROTECTION SYSTEM After installing the Rating Plug press and release the TRIP RESET push button to turn off any illuminated LEDs The purpose of the rating plug is to set the value...

Страница 16: ...the long delay current setting Ir for 40 seconds The 40 second delay allows the system to ride through momentary high load conditions and avoid nuisance alarms Long Delay Available Settings Setting 5...

Страница 17: ...gitrip RMS 910 Trip Unit whenever 120 VAC control power is not available to the Power Relay Module see Section 1 4 When a drawout circuit breaker is equipped with a Digitrip RMS 910 Trip Unit it can b...

Страница 18: ...a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM automatically reduces the time to trip to allow for the fact that the load...

Страница 19: ...function does reset rather quickly on the 0 1 second setting for example it will reset in 0 5 second 4 Test Procedures 4 1 General Danger DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUI...

Страница 20: ...al three phase circuit If three phase current had been flowing the Trip Unit would actually have performed correctly Use the APM for correct Trip Unit performance whenever single phase current injecti...

Страница 21: ...the TEST current value will be shown in the display window not the actual current flowing in the breaker 5 Reset the Trip Unit by pressing and releasing the Trip Reset push button see Figure 20 All L...

Страница 22: ...r listed in Section 6 The receiving terminal s can be An Assemblies Electronic Monitor AEM or Breaker Interface Module BIM for local or remote monitoring see Figure 22 and references in Section 6 A re...

Страница 23: ...re daisy chained interconnect shielding but do not ground the connection 1 2 watt carbon resistor required at last breaker See T D 17 513 Breaker Interface Monitor BIM OR 810 Typical IBM or IBM Twiste...

Страница 24: ...button 3 To increment the address press and release the Black DEMAND RESET push button near the display window see Figure 1 The address will increase by one unit each time you press the Black DEMAND...

Страница 25: ...I I View Power Energy Values Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X 1 2 1 3 I I Energy Consumption MWh Reverse Energy Consumption X X X X X...

Страница 26: ...RIP were initiated due to a Short Time Delay over current condition for example the coded message for SDT would be transmitted by the Trip Unit Once the message is received and interpreted by the soft...

Страница 27: ...Reset command remotely from the master computer by the INCOM lMPACC system is exactly equivalent to pressing and releasing the Trip Reset push button on the front of the Trip Unit In addition to the...

Страница 28: ...ker will trip clearing the fault in 0 5 s CASE 2 There is Zone Selective lnterlocking Fault 3 The branch breaker trip unit will initiate the trip in 0 03 s to clear the fault and Z3 will send an inter...

Страница 29: ...View values of phase currents in Display Window see Figure 1 e g 1 50 kA Note N The phase current shown will be that identified by the green LED see Figure 1 that is turned On assume IA It may not be...

Страница 30: ...t Trip Alarm contact Operator Actions 1 Observe the mode of trip LED and the INST message in the Display Window 2 Press and release the STEP push button to view current values IA IB IC and IG or ID in...

Страница 31: ...31 Instruction Leaflet I L 29 889B Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Notes...

Страница 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Отзывы: