Instruction Leaflet 

I. L. 29-889B

Effective June 2011

 Instructions for Digitrip RMS 910 Trip Unit

 

 

eaton corporation

 www.eaton.com

otee:

N

If control power is lost while you are changing the address or baud 

rate, i .e .: while you are still holding-in the "TRIP RESET" push button, the 

display will go blank and when the control power is restored, the Trip Unit will 

still retain the previous address and baud rate values, as if you had not been 

trying to change them .

NOTICE

AS SHOWN IN FIGURE 1, TO THE LEFT AND BELOW THE DISPLAY WINDOW, 

IS A SPACE TO RECORD THE INCOM ADDRESS.  BECAUSE TRIP UNITS 

AND CIRCUIT BREAKERS OF THE SAME RATING ARE INTERCHANGEABLE, 

IF MORE THAN ONE HAS BEEN WITHDRAWN FOR MAINTENANCE AT ONE 

TIME, IT IS CRITICAL THAT THE EACH UNIT BE RETURNED TO ITS CORRECT 

CELL LOCATION SO THAT THE CIRCUIT HAS THE CORRECT ADDRESS.  

FOR EXAMPLE, IF TWO IDENTICAL BREAKERS (ONE WHOSE TRIP UNIT 

ADDRESS IS "001" AND THE OTHER WHOSE TRIP UNIT ADDRESS IS 

"100") WERE SWITCHED, THE INCOM

®

 COMMUNICATIONS SYSTEM WILL 

RESPOND PER THE INFORMATION FROM EACH TRIP UNIT'S ADDRESS 

NUMBER AND NOT THE NEW CELL POSITION.

5.2  Remote Master Computer

To communicate with a remote master (IBM

®

 compatible) personal 

computer, install a Eaton Computer Operated Network Interface 

(CONI) card or Master INCOM Network Translator (MINT) into the 

computer frame (chassis) .  The connections in the network are then 

made by twisted pairs of wires as shown in Figure 21 .

5.3  Assemblies Electronic Monitor (AEM-II) and Breaker 

Interface Monitor (BIM)

An Assemblies Electronic Monitor (AEM-ll) or a Breaker Interface 

Monitor (BIM) can be applied in the same assembly with the circuit 

breakers, or at a location remote from the breakers, to monitor the 

information from any of the Digitrip RMS 910 Trip Units .  The connec-

tions in the network are made by twisted pairs of wires as shown 

in Figure 22 .  The AEM-II (Style GO4 - Firmware version 7 .1 and 

above) will display all Digitrip RMS 910 information except voltage 

and harmonic type data .  The AEM-II will pass through the voltage 

and harmonic data to a network master . Digitrip RMS 910 Trip Units 

should be set to communicate at 1200 Baud when applied on the 

same network with Digitrip RMS 700 and 800 Trip Units (see Section 

5 .1, Item 5) .

5.4  Both Remote Master Computer and AEM / BIM

When desired, Digitrip RMS 910 Trip Units can communicate with 

either an Assemblies Electronic Monitor (AEM-II) or a Breaker 

Interface Monitor (BIM) and a remote master computer (IBM PC 

compatible with CONI or MINT card as noted in Section 5 .2) .  The 

connections in the network are then made by twisted pairs of wires 

as shown in Figure 23 .

5.5  INCOM

®

 Network Interconnections

INCOM

®

 sends bursts of data on a 92 to 11 5 .2 kHz carrier at rates 

up to 9600 baud, over twisted pair conductors, to interconnect the 

many devices comprising the network .
Recommended cable specifications:

• 

Eaton cable catalog #IMPCABLE, Style #2A95705G01;

• 

Belden 9463 cable family; or

• 

Identical Commscope or Quabbin cables .

These bursts of data can be captured and used in a variety of ways 

depending upon the manner in which the master computer software 

program is written .  For example, the data for the individual phase 

current values are available on the network, but the software must 

select the appropriate data, decode and display it in a useful manner .  

Following an over-current trip operation, the sequence of coded data 

varies slightly .  The cause of trip, and the value and phase (or ground) 

current, responsible for the trip are available on the network .  If a 

TRIP were initiated due to a Short-Time Delay over-current condition, 

for example, the coded message for "SDT" would be transmitted by 

the Trip Unit .  Once the message is received and interpreted by the 

software, the value of current can be retrieved and the applicable 

phase can be identified, along with the time of trip and the value of 

the trip event counter .  As long as control power remains available to 

the Power / Relay Module, the reason for trip, and the values of cur-

rent in the other phases, including neutral and/ or ground at the time 

of trip, as well as the values of each protection setting, also remain 

available until the Trip Unit is reset .  Effective utilization of the infor-

mation available over the INCOM

®

 network requires appropriately 

designed software, such as the Eaton IMPACC

®

 system, or your own 

custom software system .
For detailed instructions about interconnecting devices over an 

INCOM

®

 network, see IMPACC

®

 wiring specification T .D . 17-513 .

5.6  lnformation Communicated by Digitrip RMS 910

The Digitrip RMS 910 Trip Unit utilizes the Eaton INCOM

®

 serialized 

protocol to send out coded messages .  The coded messages can be 

interpreted by system level software, such as the Eaton IMPACC

®

 

system, to display any of the information that is listed in Table 5 .
lnformation available for remote display includes:

• 

Status of circuit breaker: "Closed", "Open", or "Tripped";

• 

All Protection Settings (see Section 3);

• 

All information displayed in the Trip Unit window:

• 

Phase and Ground or Neutral current values,

• 

Power and Energy Demand parameter values,

• 

Coded Messages regarding status of the circuit .

Refer to the IMPACC

®

 System Communications reference program-

ming guide (see Section 6) for more information .  The information 

available through INCOM

®

 is actually greater than that available local-

ly through the Trip Unit display itself .  For example, with INCOM

®

one can view the time of trip event and trip event counter remotely, 

even though these values are not available for display locally in the 

Trip Unit window .

5.7  Waveform Capture

The Digitrip RMS 910 can respond to a command from a remote 

master to perform a waveform capture of phase currents [I

A

], [I

B

] and 

[I

C

] .  A total of 58 data points per phase per cycle is captured and 

can be sent to a host computer .  From this data, parameters such as 

[THD], individual harmonics content and waveform displays can be 

fabricated .
There is a timer in the Digitrip unit that will limit the acceptance of a 

"waveform capture" software command to once a second .  See I .L . 

17-384 Appendix U . on IMPACC System Communications on wave-

form capture commands .

5.8  Remote Closing and Tripping of Circuit Breakers

The Digitrip RMS 910 Trip Unit can respond to commands from the 

remote master computer to "TRIP" the circuit breaker remotely; 

and furthermore, if the circuit breaker has been equipped with the 

applicable optional electrical operator or spring release feature, 

the Digitrip RMS 910 Trip Unit can respond to commands from the 

remote master computer to "CLOSE" the circuit breaker remotely .  

The CLOSE command causes the "Communications Close" contact 

in the Power Relay Module to close (see wires CCI and CC2 in 

Figure 2), making the circuit breaker's closing control circuit, and 

releasing it to close (see the connection diagram applicable for your 

circuit breaker listed in Section 6) .
When the Electrical Operator or Spring Release option is purchased 

for the circuit breaker, the Communications Close contact is wired 

into the close release circuit at the factory .  The TRIP command 

causes the Digitrip RMS 910 Trip Unit to operate the circuit breaker's 

trip release (see " 

 

 

" in Figure 2) .  The trip release remains locked-

out, so that the circuit breaker cannot be reclosed, until the Trip Unit 

Содержание Digitrip RMS 910

Страница 1: ...Effective June 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 889B Instructions for Digitrip RMS 910 Trip Unit...

Страница 2: ...3 4 Short Delay Current Setting 18 3 5 Short Delay Time Setting 18 3 6 Instantaneous Current Setting 18 3 7 No Instantaneous Current Setting 19 3 8 Ground Fault Current Setting 19 3 9 Ground Fault Tim...

Страница 3: ...Figure 15 Short Delay Current Settings 16 Figure 16 Short Delay Time Settings 17 Figure 17 Instantaneous Current Settings 17 Figure 18 Ground Fault Current Settings 17 Figure 19 Ground Fault Time Dela...

Страница 4: ...urrent rating of each circuit breaker The Digitrip RMS 910 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 18...

Страница 5: ...on 1 4 will maintain the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 910 Trip Unit can be RESET in two ways Either pres...

Страница 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 9...

Страница 7: ...n Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp...

Страница 8: ...Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 910 Type Ll Figure 4 Digitrip RMS 910 Type LS Figure 5 Digitrip RMS 910 Type LSI F...

Страница 9: ...The non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approxi mately ten 10 cycles following the initial current flow through...

Страница 10: ...ppendix A 1 2 Four Character Information Display Window The four digit alpha numeric display window illustrated in Figures 1 and 2 serves two basic purposes instrumentation and mode of trip and troubl...

Страница 11: ...wer Power Factor and Energy Values 1 2 1 3 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X Power Factor X X X X X X 1 2 1 3 Energy Consumption MWh Rev...

Страница 12: ...lug is missing damaged or not well connected If breaker is closed it will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Pr...

Страница 13: ...l in Figure 1 Note N The peak demand function requires that 120 VAC control power be sup plied to the Power 1 Relay Module The Present Demand is a power value averaged over approximately one second To...

Страница 14: ...elease of the Step push button will initiate a 3 phase waveform capture internally in the Digitrip and in turn calculate all THD and individual values Notice that two Green LEDs THD and IA are now ill...

Страница 15: ...D OR FAILURE OF THE PROTECTION SYSTEM After installing the Rating Plug press and release the TRIP RESET push button to turn off any illuminated LEDs The purpose of the rating plug is to set the value...

Страница 16: ...the long delay current setting Ir for 40 seconds The 40 second delay allows the system to ride through momentary high load conditions and avoid nuisance alarms Long Delay Available Settings Setting 5...

Страница 17: ...gitrip RMS 910 Trip Unit whenever 120 VAC control power is not available to the Power Relay Module see Section 1 4 When a drawout circuit breaker is equipped with a Digitrip RMS 910 Trip Unit it can b...

Страница 18: ...a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM automatically reduces the time to trip to allow for the fact that the load...

Страница 19: ...function does reset rather quickly on the 0 1 second setting for example it will reset in 0 5 second 4 Test Procedures 4 1 General Danger DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUI...

Страница 20: ...al three phase circuit If three phase current had been flowing the Trip Unit would actually have performed correctly Use the APM for correct Trip Unit performance whenever single phase current injecti...

Страница 21: ...the TEST current value will be shown in the display window not the actual current flowing in the breaker 5 Reset the Trip Unit by pressing and releasing the Trip Reset push button see Figure 20 All L...

Страница 22: ...r listed in Section 6 The receiving terminal s can be An Assemblies Electronic Monitor AEM or Breaker Interface Module BIM for local or remote monitoring see Figure 22 and references in Section 6 A re...

Страница 23: ...re daisy chained interconnect shielding but do not ground the connection 1 2 watt carbon resistor required at last breaker See T D 17 513 Breaker Interface Monitor BIM OR 810 Typical IBM or IBM Twiste...

Страница 24: ...button 3 To increment the address press and release the Black DEMAND RESET push button near the display window see Figure 1 The address will increase by one unit each time you press the Black DEMAND...

Страница 25: ...I I View Power Energy Values Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X 1 2 1 3 I I Energy Consumption MWh Reverse Energy Consumption X X X X X...

Страница 26: ...RIP were initiated due to a Short Time Delay over current condition for example the coded message for SDT would be transmitted by the Trip Unit Once the message is received and interpreted by the soft...

Страница 27: ...Reset command remotely from the master computer by the INCOM lMPACC system is exactly equivalent to pressing and releasing the Trip Reset push button on the front of the Trip Unit In addition to the...

Страница 28: ...ker will trip clearing the fault in 0 5 s CASE 2 There is Zone Selective lnterlocking Fault 3 The branch breaker trip unit will initiate the trip in 0 03 s to clear the fault and Z3 will send an inter...

Страница 29: ...View values of phase currents in Display Window see Figure 1 e g 1 50 kA Note N The phase current shown will be that identified by the green LED see Figure 1 that is turned On assume IA It may not be...

Страница 30: ...t Trip Alarm contact Operator Actions 1 Observe the mode of trip LED and the INST message in the Display Window 2 Press and release the STEP push button to view current values IA IB IC and IG or ID in...

Страница 31: ...31 Instruction Leaflet I L 29 889B Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Notes...

Страница 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Отзывы: