Instruction Leaflet 

I. L. 29-889B

Effective June 2011

 Instructions for Digitrip RMS 910 Trip Unit

 

 

eaton corporation

 www.eaton.com

sensor rating, the Trip Unit will trip the breaker again .
As indicated in Figures 2 and 9, a back-up battery is provided to 

maintain the mode of trip LED indication in the Digitrip RMS 910 Trip 

Unit when external control power to the Power / Relay module is not 

available .  The back-up battery is located in the rating plug along with 

a battery check push-button and a green battery check LED .  The bat-

tery in the rating plug is "OK" if the LED lights "Green" when the "bat-

tery check" button next to it is pushed (see Section 4 .5) .

otee:

N

The battery is used only to maintain the cause of TRIP LED indication .  

It has NO part in the PROTECTION FUNCTION of the Trip Unit, and, it does 

NOT light the display window .

1.4  Power / Relay Module

The Power / Relay Module (PRM) (see Figure 10) is separate from 

the RMS Digitrip 910 Trip Unit itself, and is 

not required

 for the Trip 

Unit to perform its 

protection functions

 .  The Power / Relay Module 

performs two functions .  First, it uses available external control 

power (120 V 50/60 Hz ac, 6 VA) to operate the display window, com-

munications circuitry, and reason for trip LED indicators .  Second, 

it provides relay contacts for use by other devices remote from the 

circuit breaker .

NOTICE

THE POWER / RELAY MODULE HAS 120 V 50/60 HZ AC INPUT AS STANDARD 

FOR ALL BREAKER TYPES.  THERE IS AVAILABLE FOR CERTAIN BREAKER 

TYPES A 230 V 50/60 INPUT VOLTAGE RATING.  BEFORE ENERGIZING 

THIS CONTROL VOLTAGE, PLEASE VERIFY CORRECT VOLTAGE RATING IS 

EMPLOYED.  THE DISPLAY, COMMUNICATION, OR TRIP RELAY ALARMS 

MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED.

Figure 13. Long Delay Current Settings.

The relays operate when the Trip Unit detects the following condi-

tions, as shown in Figure 2:

• 

Short-Circuit Trip Alarm

• 

High Load Alarm

• 

Long Delay Trip Alarm

• 

Ground fault Trip Alarm (types LIG, LSG, LSIG) or Neutral Over-

Current Alarm (types LI, LS LSI)

• 

In addition, the Power / Relay Module also contains the INCOM® 

COMMUNICATIONS CLOSE contact, which operates the circuit 

breaker's closing release, on command from INCOM / IMPACC® 

(see Section 5 .8 .) .

Each relay contact is rated for 120 V, 50/60 Hz ac, 1 .0 Ampere .  The 

High Load Alarm contact operates after the load current has exceed-

ed 85% of the long delay current setting,

 I

r

  for 40 seconds .  The 

40-second delay allows the system to "ride through" momentary high 

load conditions and avoid nuisance alarms .

Long Delay

Available Settings 

Setting

.5, ,6, .7, .8,

.85, .9, .95, 1

In Multiples of

Rating Plug

Amperes

I

r

I

r

I

r

I

n

(I  )

n

I

r

The Long Delay Trip Alarm contact operates after the breaker TRIPS 

due to over-load conditions which exceeded the Long Delay Trip set-

tings .
For Type LSG, LIG, and LSIG Trip Units, the Ground Fault Trip Alarm 

contact operates after the breaker TRIPS due to conditions which 

exceed the Ground Fault protection settings .  For Type LS, LI, and 

LSI Trip Units, the Neutral Current Alarm contact operates when the 

neutral current exceeds the Long Delay Current protection setting, 

I

r

 .

Figure 14. Long Delay Time Settings.

Figure 15. Short Delay Current Settings.

The Short-Circuit Trip Alarm contact operates after the breaker TRIPS 

due to an INSTantaneous trip, Short-Delay Trip, DlSCriminator trip, a 

Fixed Instantaneous OverRlDe trip, or a Rating PLUG trip as appli-

cable .
Even without available external control power, once the load cur-

rent through the circuit breaker exceeds approximately 20% (40% 

if single phase) of the frame / current sensor rating, the green LED 

will flash "On and Off" once each second, to indicate the Trip Unit 

is energized and operating properly, and all protection functions are 

functioning .  However, the display window will remain dark .

otee:

N

If 120 VAC control power is lost to the Power / Relay Module, the 

LOCKOUT after trip will reset and the breaker can be closed again .  However 

the cause of trip bit will remain set in the Digitrip's non-volatile memory and a 

cause of trip message will reappear when control power returns .  A complete 

clearing of cause of trip history may be accomplished by depressing the reset 

push-button when the Digitrip unit is powered up (indicated by the Unit Status 

flashing) .

1.5  Potential Transformer Module

The Potential Transformer Module (PTM) (see Figure 11) is also 

separate from the RMS 910 Trip Unit and is not required for the Trip 

Unit to perform its protection functions .  The Potential Transformer 

Module provides three-phase primary voltage information necessary 

for the Trip Unit to calculate power and energy values (see Figure 2) .

.

,

,

Available Settings 

12, 15, 20, 24

I...

Seconds at

6 Times

,

.

. .

.

.

6

x

Long

Time

Delay

Sec.

at 6 x

I

r

I

r

4

(I  )

r

Long Delay Setting

2, 4, 7, 10,

.  . 

S1 and S2

2, 2.5, 3, 4

Available Settings 

.  . 

.

Setting

In Multiples of

Long Delay Setting

Values are Specified on Rating Plug

5, 6, S  , S

1

2

I

r

(I  )

r

Содержание Digitrip RMS 910

Страница 1: ...Effective June 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 889B Instructions for Digitrip RMS 910 Trip Unit...

Страница 2: ...3 4 Short Delay Current Setting 18 3 5 Short Delay Time Setting 18 3 6 Instantaneous Current Setting 18 3 7 No Instantaneous Current Setting 19 3 8 Ground Fault Current Setting 19 3 9 Ground Fault Tim...

Страница 3: ...Figure 15 Short Delay Current Settings 16 Figure 16 Short Delay Time Settings 17 Figure 17 Instantaneous Current Settings 17 Figure 18 Ground Fault Current Settings 17 Figure 19 Ground Fault Time Dela...

Страница 4: ...urrent rating of each circuit breaker The Digitrip RMS 910 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 18...

Страница 5: ...on 1 4 will maintain the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 910 Trip Unit can be RESET in two ways Either pres...

Страница 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 9...

Страница 7: ...n Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp...

Страница 8: ...Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 910 Type Ll Figure 4 Digitrip RMS 910 Type LS Figure 5 Digitrip RMS 910 Type LSI F...

Страница 9: ...The non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approxi mately ten 10 cycles following the initial current flow through...

Страница 10: ...ppendix A 1 2 Four Character Information Display Window The four digit alpha numeric display window illustrated in Figures 1 and 2 serves two basic purposes instrumentation and mode of trip and troubl...

Страница 11: ...wer Power Factor and Energy Values 1 2 1 3 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X Power Factor X X X X X X 1 2 1 3 Energy Consumption MWh Rev...

Страница 12: ...lug is missing damaged or not well connected If breaker is closed it will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Pr...

Страница 13: ...l in Figure 1 Note N The peak demand function requires that 120 VAC control power be sup plied to the Power 1 Relay Module The Present Demand is a power value averaged over approximately one second To...

Страница 14: ...elease of the Step push button will initiate a 3 phase waveform capture internally in the Digitrip and in turn calculate all THD and individual values Notice that two Green LEDs THD and IA are now ill...

Страница 15: ...D OR FAILURE OF THE PROTECTION SYSTEM After installing the Rating Plug press and release the TRIP RESET push button to turn off any illuminated LEDs The purpose of the rating plug is to set the value...

Страница 16: ...the long delay current setting Ir for 40 seconds The 40 second delay allows the system to ride through momentary high load conditions and avoid nuisance alarms Long Delay Available Settings Setting 5...

Страница 17: ...gitrip RMS 910 Trip Unit whenever 120 VAC control power is not available to the Power Relay Module see Section 1 4 When a drawout circuit breaker is equipped with a Digitrip RMS 910 Trip Unit it can b...

Страница 18: ...a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM automatically reduces the time to trip to allow for the fact that the load...

Страница 19: ...function does reset rather quickly on the 0 1 second setting for example it will reset in 0 5 second 4 Test Procedures 4 1 General Danger DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUI...

Страница 20: ...al three phase circuit If three phase current had been flowing the Trip Unit would actually have performed correctly Use the APM for correct Trip Unit performance whenever single phase current injecti...

Страница 21: ...the TEST current value will be shown in the display window not the actual current flowing in the breaker 5 Reset the Trip Unit by pressing and releasing the Trip Reset push button see Figure 20 All L...

Страница 22: ...r listed in Section 6 The receiving terminal s can be An Assemblies Electronic Monitor AEM or Breaker Interface Module BIM for local or remote monitoring see Figure 22 and references in Section 6 A re...

Страница 23: ...re daisy chained interconnect shielding but do not ground the connection 1 2 watt carbon resistor required at last breaker See T D 17 513 Breaker Interface Monitor BIM OR 810 Typical IBM or IBM Twiste...

Страница 24: ...button 3 To increment the address press and release the Black DEMAND RESET push button near the display window see Figure 1 The address will increase by one unit each time you press the Black DEMAND...

Страница 25: ...I I View Power Energy Values Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X 1 2 1 3 I I Energy Consumption MWh Reverse Energy Consumption X X X X X...

Страница 26: ...RIP were initiated due to a Short Time Delay over current condition for example the coded message for SDT would be transmitted by the Trip Unit Once the message is received and interpreted by the soft...

Страница 27: ...Reset command remotely from the master computer by the INCOM lMPACC system is exactly equivalent to pressing and releasing the Trip Reset push button on the front of the Trip Unit In addition to the...

Страница 28: ...ker will trip clearing the fault in 0 5 s CASE 2 There is Zone Selective lnterlocking Fault 3 The branch breaker trip unit will initiate the trip in 0 03 s to clear the fault and Z3 will send an inter...

Страница 29: ...View values of phase currents in Display Window see Figure 1 e g 1 50 kA Note N The phase current shown will be that identified by the green LED see Figure 1 that is turned On assume IA It may not be...

Страница 30: ...t Trip Alarm contact Operator Actions 1 Observe the mode of trip LED and the INST message in the Display Window 2 Press and release the STEP push button to view current values IA IB IC and IG or ID in...

Страница 31: ...31 Instruction Leaflet I L 29 889B Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Notes...

Страница 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Отзывы: