background image

10

Instruction Leaflet 

I. L. 29-889B

Effective June 2011

 Instructions for Digitrip RMS 910 Trip Unit

 

 

eaton corporation

 www.eaton.com

1.1.4  OVERRIDE (Fixed Instantaneous)

Each Digitrip RMS 910 Trip Unit has a Fixed Instantaneous "Override" 

analog trip circuit pre-set to a value no greater than the short-time 

withstand current rating of the circuit breaker in which the Trip Unit 

is installed .  Since the specific values vary for different circuit break-

er types and ratings, refer to time-current curves, listed in Section 6, 

for the values applicable to your breaker .  If the breaker trips due to 

high instantaneous current, the "

OVERRIDE/

" LED will light "RED", 

and the display will read "

ORID

" .

1.1.5  Zone Interlocking

Zone Selective lnterlocking (or Zone Interlocking) is available (see 

Figure 2) for Digitrip RMS Trip Units having Short Delay and/or 

Ground Fault protection .  Zone Selective lnterlocking provides the 

fastest possible tripping for faults within the breaker's zone of pro-

tection, and yet also provides positive coordination among all break-

ers in the system (mains, ties, feeders and downstream breakers) to 

limit the outage to the affected part of the system only .  When Zone 

lnterlocking is enabled, a fault within the breaker's zone of protection 

will cause the Trip Unit to:

• 

Trip the affected breaker instantaneously, and

• 

Send a signal to upstream RMS Digitrip Trip Units to restrain from 

tripping immediately .  The restraining signal causes the upstream 

breakers to follow their set coordination times, so that only the 

minimum service is disrupted, while the fault is cleared in the 

shortest time possible .

This signal requires that only a single pair of wires be connected 

from the interlock output terminals of the downstream breaker's 

Trip Unit, to the interlock input terminals of the upstream breaker's 

Trip Unit .  For specific instructions see the applicable connection dia-

grams for your breaker listed in Section 6 .

otee:

N

If a breaker (M) receives a Zone lnterlocking signal from another 

breaker (F) that is tripping, but the fault current level is less than the setting 

for breaker (M), the presence of the Zone lnterlocking signal from the other 

breaker (F) can not cause breaker (M) to trip .

 CAUTION

IF ZONE INTERLOCKING IS NOT TO BE USED (I.E.: STANDARD TIME-

DELAY COORDINATION ONLY IS INTENDED), THE ZONE INTERLOCKING 

TERMINALS MUST BE CONNECTED WITH JUMPER WIRES, AS SPECIFIED 

ON THE CONNECTION DIAGRAMS FOR YOUR BREAKER (SEE SECTION 

6), SO THE TIME DELAY SETTINGS WILL PROVIDE THE INTENDED 

COORDINATION.

For examples of how Zone Selective lnterlocking may be used, See 

Appendix A .

1.2  Four Character Information Display Window

The four-digit alpha-numeric display window, illustrated in Figures 1 

and 2, serves two basic purposes: instrumentation and mode of trip 

and trouble indication .  The information displayed in the window is 

listed in Tables 2 and 3 .

1.2.1  Values Displayed During Normal Service

The alpha-numeric display window provides informational values 

under normal service conditions and coded messages after an alarm 

condition or after an over-current trip operation .  The 12 Green LEDs 

below the display window indicate which value of current, voltage, 

power, power factor, energy, or Total Harmonic Distortion (THD) is 

being displayed .  The value in the display window indicates the pres-

ent value of the parameter whose LED is lighted "Green" .  In Figure 

1, the first four "Green" LEDs identify which current 

(kA)

 value is 

being displayed, i .e .: phase A current 

(I

A

)

, phase B current 

(I

B

)

phase C current 

(I

C

)

, ground current 

(I

G

)

, or current in the fourth pole 

(neutral) 

(I

D

)

 .  The press and release operation of the "Step" push-

button will step next to the Green LEDs that identify the breaker's 

phase to phase voltages being displayed; i .e .: (V

AB

), (V

BC

), (V

CA

) . 

Values are in volts RMS .
A repeat press and release of "Step" pushbutton will proceed to the 

four Green LEDs that identify Peak Power Demand (MW), Present 

Power Demand (MW), Energy Demand (MWh), and Power Factor 

(PF) .  The next press and release of "Step" push-button will show the 

(THD) for phase 

(I

A

)

 current .  Notice that both the green LEDs (THD) 

and 

(I

A

)

 are illuminated .  Repeating "Step" push-button operation will 

show (THD) values for 

(I

B

)

 and 

(I

C

)

 currents . Repeating press and 

release one more time will sequence back from the (THD) of 

(I

C

)

 to 

the 

(kA)

 current of 

(I

A

)

 . See Section 1 .2 .1 .4 for displaying per har-

monic data .

1.2.1.1  Instrumentation - Current Values

During the normal service conditions, with the circuit breaker closed, 

the Digitrip 910 serves as an ammeter, displaying the individual 

phase currents (I

A

, I

B

, I

C

) and ground current (I

G

) or the fourth pole 

(neutral) current 

(I

D

)

, provided the circuit breaker is set up for ground 

or fourth pole protection .  Current values are displayed in kA .  The 

value displayed is current in the pole (or ground) indicated by the 

"Green" LED that is turned "On" .  Press and release the (Black) 

"STEP" push-button to view the values of current in the other phases 

(see Figure 1) .  The range, accuracy and wave shape parameters for 

current values displayed are:

 

RANGE:  0 to 9 .999 kA if I

n

  

 1000 A 

 

 

0 to 99 .99 kA if I

n

  >1000A

  ASSUMES:  5% < Current < 100% of Frame Rating for Series 

     

C

®

 R-Frame or Type SPB circuit breaker .

 

   

or

 

   

5% < Current < 100% of [Current] Sensor Rating 

 

   

for Type DS circuit breaker .

  ACCURACY:  ± 2% of Frame Rating for Series C

®

 R-Frame or

   

 

Type SPB circuit breakers .

   

 

or

   

 

± 2% of [Current] Sensor Rating for Type DS  

   

 

circuit breaker .

Содержание Digitrip RMS 910

Страница 1: ...Effective June 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 889B Instructions for Digitrip RMS 910 Trip Unit...

Страница 2: ...3 4 Short Delay Current Setting 18 3 5 Short Delay Time Setting 18 3 6 Instantaneous Current Setting 18 3 7 No Instantaneous Current Setting 19 3 8 Ground Fault Current Setting 19 3 9 Ground Fault Tim...

Страница 3: ...Figure 15 Short Delay Current Settings 16 Figure 16 Short Delay Time Settings 17 Figure 17 Instantaneous Current Settings 17 Figure 18 Ground Fault Current Settings 17 Figure 19 Ground Fault Time Dela...

Страница 4: ...urrent rating of each circuit breaker The Digitrip RMS 910 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 18...

Страница 5: ...on 1 4 will maintain the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 910 Trip Unit can be RESET in two ways Either pres...

Страница 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 9...

Страница 7: ...n Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp...

Страница 8: ...Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 910 Type Ll Figure 4 Digitrip RMS 910 Type LS Figure 5 Digitrip RMS 910 Type LSI F...

Страница 9: ...The non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approxi mately ten 10 cycles following the initial current flow through...

Страница 10: ...ppendix A 1 2 Four Character Information Display Window The four digit alpha numeric display window illustrated in Figures 1 and 2 serves two basic purposes instrumentation and mode of trip and troubl...

Страница 11: ...wer Power Factor and Energy Values 1 2 1 3 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X Power Factor X X X X X X 1 2 1 3 Energy Consumption MWh Rev...

Страница 12: ...lug is missing damaged or not well connected If breaker is closed it will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Pr...

Страница 13: ...l in Figure 1 Note N The peak demand function requires that 120 VAC control power be sup plied to the Power 1 Relay Module The Present Demand is a power value averaged over approximately one second To...

Страница 14: ...elease of the Step push button will initiate a 3 phase waveform capture internally in the Digitrip and in turn calculate all THD and individual values Notice that two Green LEDs THD and IA are now ill...

Страница 15: ...D OR FAILURE OF THE PROTECTION SYSTEM After installing the Rating Plug press and release the TRIP RESET push button to turn off any illuminated LEDs The purpose of the rating plug is to set the value...

Страница 16: ...the long delay current setting Ir for 40 seconds The 40 second delay allows the system to ride through momentary high load conditions and avoid nuisance alarms Long Delay Available Settings Setting 5...

Страница 17: ...gitrip RMS 910 Trip Unit whenever 120 VAC control power is not available to the Power Relay Module see Section 1 4 When a drawout circuit breaker is equipped with a Digitrip RMS 910 Trip Unit it can b...

Страница 18: ...a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM automatically reduces the time to trip to allow for the fact that the load...

Страница 19: ...function does reset rather quickly on the 0 1 second setting for example it will reset in 0 5 second 4 Test Procedures 4 1 General Danger DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUI...

Страница 20: ...al three phase circuit If three phase current had been flowing the Trip Unit would actually have performed correctly Use the APM for correct Trip Unit performance whenever single phase current injecti...

Страница 21: ...the TEST current value will be shown in the display window not the actual current flowing in the breaker 5 Reset the Trip Unit by pressing and releasing the Trip Reset push button see Figure 20 All L...

Страница 22: ...r listed in Section 6 The receiving terminal s can be An Assemblies Electronic Monitor AEM or Breaker Interface Module BIM for local or remote monitoring see Figure 22 and references in Section 6 A re...

Страница 23: ...re daisy chained interconnect shielding but do not ground the connection 1 2 watt carbon resistor required at last breaker See T D 17 513 Breaker Interface Monitor BIM OR 810 Typical IBM or IBM Twiste...

Страница 24: ...button 3 To increment the address press and release the Black DEMAND RESET push button near the display window see Figure 1 The address will increase by one unit each time you press the Black DEMAND...

Страница 25: ...I I View Power Energy Values Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X 1 2 1 3 I I Energy Consumption MWh Reverse Energy Consumption X X X X X...

Страница 26: ...RIP were initiated due to a Short Time Delay over current condition for example the coded message for SDT would be transmitted by the Trip Unit Once the message is received and interpreted by the soft...

Страница 27: ...Reset command remotely from the master computer by the INCOM lMPACC system is exactly equivalent to pressing and releasing the Trip Reset push button on the front of the Trip Unit In addition to the...

Страница 28: ...ker will trip clearing the fault in 0 5 s CASE 2 There is Zone Selective lnterlocking Fault 3 The branch breaker trip unit will initiate the trip in 0 03 s to clear the fault and Z3 will send an inter...

Страница 29: ...View values of phase currents in Display Window see Figure 1 e g 1 50 kA Note N The phase current shown will be that identified by the green LED see Figure 1 that is turned On assume IA It may not be...

Страница 30: ...t Trip Alarm contact Operator Actions 1 Observe the mode of trip LED and the INST message in the Display Window 2 Press and release the STEP push button to view current values IA IB IC and IG or ID in...

Страница 31: ...31 Instruction Leaflet I L 29 889B Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Notes...

Страница 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Отзывы: