23
Instruction Leaflet
I. L. 29-889B
Effective June 2011
Instructions for Digitrip RMS 910 Trip Unit
eaton corporation
www.eaton.com
Figure 22. INCOM Network with AEM / BIM.
Figure 23. INCOM Network with Remote Master Computer and AEM / BIM.
Twisted Pair.
Cut-off Shield at
Device Do Not Ground
Circuit
Breaker
RMS 800
See Section
Trip Unit
Note: OK t o mix Models 700, 800, and 810 Trip Units i f Baud Rate L = 1200 is used.
Refer t o circuit breaker connection diagrams referenced in Section 6 for actual connections.
Ground shielding at
AEM/BIM
only as shown. Where devices are daisy-chained,
interconnect shielding, but do not ground the connection.
1/2 watt carbon resistor required at last breaker. See T.D. 17-513.
Breaker
Interface
Monitor
(BIM)
OR
810
Typical IBM (or IBM
Twisted Pair.
No.
18 AWG. (See Section
5.5
for cable specifications.)
----
Cut-off Shield at
Device -D o Not Ground
See Section
Refer to circuit breaker connection diagrams referenced in Section
6
for actual connections.
Modular telephone connector, Type RJ11, supplied by User.
Grounded shielding at computer and AEM / BIM (cable to P1 only) as shown. Where devices are daisy-chained, interconnect shielding,
but do not ground the connection.
1/2 watt carbon resistor required at last breaker. See T.D. 17-513.
CONI Card
Assemblies
Electronic
Monitor
(AEM)
or
Breaker
Interface
Monitor
(BIM)