background image

13

Instruction Leaflet 

I. L. 29-889B

Effective June 2011

 Instructions for Digitrip RMS 910 Trip Unit

 

 

eaton corporation

 www.eaton.com

CAUTION

WHEN THE CIRCUIT BREAKER'S CONTACTS ARE OPEN IT MAY OR MAY NOT DISPLAY 

THE BREAKER'S PHASE TO PHASE VOLTAGES.  THIS DEPENDS ON THE BREAKER 

TYPE.  THE TYPE DS BREAKERS PICK UP THE PT MODULE’S CONNECTIONS ON THE 

TOP SIDE WHILE THE TYPES SPB AND RD BREAKERS PT MODULE IS CONNECTED TO 

THE BOTTOM SIDE (SEE FIGURE 2).  A SECOND FACTOR TO CONSIDER IS WHETHER 

THE BREAKER IS REVERSE FED IN APPLICATION.  THEREFORE DO NOT RELY UPON 

THE VOLTAGE READOUT AS A SOLE INDICATOR OF THE BREAKER'S ON/OFF STATUS 

OR BREAKER'S VOLTAGE STATUS.

1.2.1.3  Instrumentation - Power, Power Factor and Energy 

Values

The Digitrip RMS 910 Trip Unit displays power and energy values .  By 

using the circuit breaker current sensors and an integrally mounted 

Potential Transformer Module shown in Figure 11, power and energy 

values are computed and displayed in the four-digit display window 

on the face of the Trip Unit .
The power, power factor and energy parameter values displayed in 

the window on the face of the Trip Unit include:

• 

Peak Demand in MW (Megawatts),

• 

Present Demand in MW (Megawatts),

• 

Energy (Consumed) in MWh (Megawatt-hours), and

• 

Power Factor .

Four "Green" LEDs, as shown in Figure 1, are provided to indicate 

which value is displayed .  The same "STEP" push-button pressed and 

released to view the different values of current and voltage is also 

pressed and released to view the power, power factor and energy 

values .
The 

Peak Demand

 parameter is based on a sampling window of 

fifteen (15) minutes .  Power is repeatedly averaged over this inter-

val and the maximum average is displayed as Peak Demand .  The 

demand window is not a "sliding window" . It is more like a 'jumping 

window" .  When the Trip Unit is first energized, there is a delay of 

15 minutes before the first non-zero value is displayed .  To reset the 

peak demand value shown in the display window back to zero, press 

and release the (Black) "Demand Reset" push-button, shown adjacent 

to the "Peak Demand" label in Figure 1 .

otee:

N

The peak demand function requires that 120 VAC control power be sup-

plied to the Power 1 Relay Module .

The 

Present Demand

 is a power value averaged over approximately 

one second .  To view the "Present Demand" value in the display win-

dow, press and release the "STEP" push-button several times until 

the LED next to "Present MW” is lighted .
The range, assumptions and accuracy parameters for peak and pres-

ent power demand values displayed are:
Range-    

 0 to 9 .999 MW

Assumes - 

 5% < Current < 175% of the Plug Rating I

n

Sampling Window-  

15 min.

 for 

Peak Demand, ~1 sec.

 for 

 

 

 Present Demand

Accuracy- 

 

± 4%

 of (Frame Rating x 600 V) for Series C

®

 

 

 R-Frame or Type SPB circuit breakers,

 

or 

 

± 4%

 of (Current Sensor Rating x 600 V) for Type 

 

 

 DS circuit breakers .

The System Power Factor 

(PF)

 is a unitless parameter that is dis-

played locally on the Digitrip RMS 910 .  The range assumptions and 

accuracy for the system power factor function values are:
Range-    From 0 .5 (lagging) to 0 .5 (leading)
Assumes- 

 Balanced three-phase load, per ANSI Std . C 12 .1- 

 1988

Current- 

 > 20% of Frame Rating for Series C

®

 R-Frame or Type 

 SPB circuit breakers .

Current- 

 20% of [Current] Sensor Rating for Type DS circuit  

 breakers .

Accuracy- 

 ± 0.02

The 

Energy

 parameter is the summation of the average power over 

time and it is expressed in megawatt-hours (MWh) .  The value is 

updated approximately once a second .  The value cannot be reset 

locally .  After the maximum value is reached, the display automati-

cally rolls over to zero .
The range and accuracy parameters for energy demand values dis-

played are:
Range- 

0 to 999 .9 MWh if I

n

 < 1000 A 

0 to 9999 MWh if I

n

 > 1000 A

Assumes- 

5% < Current < 175% of the Plug Rating I

n

Accuracy- 

± 5% of (Frame Rating x 600 V x time) for Series  

 C

®

 R-Frame or Type SPB circuit breakers .

or 

± 5% of (Current Sensor Rating x 600 V x time)  

for Type DS circuit breakers .

Polarity

Figure 9. Rating Plug.

Polarity 

Marks

Hinged 

Cover

Battery

Rating Plug 

is for Type 

SPB Circuit 

Breakers Only

Rating Plug 

for R-Frame 

and DS 

Breakers 

are Similar

Values for Short 

Delay S1 and S2 

Instantaneous 

M1 and M2 

Settings

Pull Tab to 

Remove 

Battery

Rating Plug 

Identification

"Battery 

Check" 

Push 

button

Battery "OK" 

if LED Lights 

"GREEN" when 

"Battery Check" 

Button is 

Pushed

Rating Plug 

Retention 

Screw

Battery 

Removal Tab

Polarity

-

+

Содержание Digitrip RMS 910

Страница 1: ...Effective June 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 889B Instructions for Digitrip RMS 910 Trip Unit...

Страница 2: ...3 4 Short Delay Current Setting 18 3 5 Short Delay Time Setting 18 3 6 Instantaneous Current Setting 18 3 7 No Instantaneous Current Setting 19 3 8 Ground Fault Current Setting 19 3 9 Ground Fault Tim...

Страница 3: ...Figure 15 Short Delay Current Settings 16 Figure 16 Short Delay Time Settings 17 Figure 17 Instantaneous Current Settings 17 Figure 18 Ground Fault Current Settings 17 Figure 19 Ground Fault Time Dela...

Страница 4: ...urrent rating of each circuit breaker The Digitrip RMS 910 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 18...

Страница 5: ...on 1 4 will maintain the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 910 Trip Unit can be RESET in two ways Either pres...

Страница 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 9...

Страница 7: ...n Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp...

Страница 8: ...Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 910 Type Ll Figure 4 Digitrip RMS 910 Type LS Figure 5 Digitrip RMS 910 Type LSI F...

Страница 9: ...The non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approxi mately ten 10 cycles following the initial current flow through...

Страница 10: ...ppendix A 1 2 Four Character Information Display Window The four digit alpha numeric display window illustrated in Figures 1 and 2 serves two basic purposes instrumentation and mode of trip and troubl...

Страница 11: ...wer Power Factor and Energy Values 1 2 1 3 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X Power Factor X X X X X X 1 2 1 3 Energy Consumption MWh Rev...

Страница 12: ...lug is missing damaged or not well connected If breaker is closed it will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Pr...

Страница 13: ...l in Figure 1 Note N The peak demand function requires that 120 VAC control power be sup plied to the Power 1 Relay Module The Present Demand is a power value averaged over approximately one second To...

Страница 14: ...elease of the Step push button will initiate a 3 phase waveform capture internally in the Digitrip and in turn calculate all THD and individual values Notice that two Green LEDs THD and IA are now ill...

Страница 15: ...D OR FAILURE OF THE PROTECTION SYSTEM After installing the Rating Plug press and release the TRIP RESET push button to turn off any illuminated LEDs The purpose of the rating plug is to set the value...

Страница 16: ...the long delay current setting Ir for 40 seconds The 40 second delay allows the system to ride through momentary high load conditions and avoid nuisance alarms Long Delay Available Settings Setting 5...

Страница 17: ...gitrip RMS 910 Trip Unit whenever 120 VAC control power is not available to the Power Relay Module see Section 1 4 When a drawout circuit breaker is equipped with a Digitrip RMS 910 Trip Unit it can b...

Страница 18: ...a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM automatically reduces the time to trip to allow for the fact that the load...

Страница 19: ...function does reset rather quickly on the 0 1 second setting for example it will reset in 0 5 second 4 Test Procedures 4 1 General Danger DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUI...

Страница 20: ...al three phase circuit If three phase current had been flowing the Trip Unit would actually have performed correctly Use the APM for correct Trip Unit performance whenever single phase current injecti...

Страница 21: ...the TEST current value will be shown in the display window not the actual current flowing in the breaker 5 Reset the Trip Unit by pressing and releasing the Trip Reset push button see Figure 20 All L...

Страница 22: ...r listed in Section 6 The receiving terminal s can be An Assemblies Electronic Monitor AEM or Breaker Interface Module BIM for local or remote monitoring see Figure 22 and references in Section 6 A re...

Страница 23: ...re daisy chained interconnect shielding but do not ground the connection 1 2 watt carbon resistor required at last breaker See T D 17 513 Breaker Interface Monitor BIM OR 810 Typical IBM or IBM Twiste...

Страница 24: ...button 3 To increment the address press and release the Black DEMAND RESET push button near the display window see Figure 1 The address will increase by one unit each time you press the Black DEMAND...

Страница 25: ...I I View Power Energy Values Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X 1 2 1 3 I I Energy Consumption MWh Reverse Energy Consumption X X X X X...

Страница 26: ...RIP were initiated due to a Short Time Delay over current condition for example the coded message for SDT would be transmitted by the Trip Unit Once the message is received and interpreted by the soft...

Страница 27: ...Reset command remotely from the master computer by the INCOM lMPACC system is exactly equivalent to pressing and releasing the Trip Reset push button on the front of the Trip Unit In addition to the...

Страница 28: ...ker will trip clearing the fault in 0 5 s CASE 2 There is Zone Selective lnterlocking Fault 3 The branch breaker trip unit will initiate the trip in 0 03 s to clear the fault and Z3 will send an inter...

Страница 29: ...View values of phase currents in Display Window see Figure 1 e g 1 50 kA Note N The phase current shown will be that identified by the green LED see Figure 1 that is turned On assume IA It may not be...

Страница 30: ...t Trip Alarm contact Operator Actions 1 Observe the mode of trip LED and the INST message in the Display Window 2 Press and release the STEP push button to view current values IA IB IC and IG or ID in...

Страница 31: ...31 Instruction Leaflet I L 29 889B Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Notes...

Страница 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Отзывы: