background image

9

Instruction Leaflet 

I. L. 29-889B

Effective June 2011

 Instructions for Digitrip RMS 910 Trip Unit

 

 

eaton corporation

 www.eaton.com

Figure 7. Digitrip RMS 910 Type LSG.

Figure 8. Digitrip RMS 910 Type LSIG.

NOTICE

AFTER EACH TRIP OPERATION (WHETHER DUE TO OVERCURRENT 

PROTECTION OR REMOTE CONTROL) THE AUTOMATIC LOCKOUT-AFTER-

TRIP FEATURE OF THE DIGITRIP RMS 910 TRIP UNIT MAINTAINS THE 

CIRCUIT BREAKER IN A "TRIP-FREE" CONDITION, PROVIDED 120 VAC 

CONTROL POWER REMAINS AVAILABLE TO THE POWER / RELAY MODULE.  

THE TRIP UNIT MUST BE RESET BEFORE THE CIRCUIT BREAKER CAN BE 

CLOSED AGAIN. THE RESET CAN BE ACCOMPLISHED EITHER LOCALLY BY 

PRESSING AND RELEASING THE "TRIP RESET' PUSH BUTTON (SEE FIGURE 

1),OR REMOTELY BY THE IMPACC SYSTEM (SEE SECTION 5.9).

After an over-current trip operation, the following information is 

stored in the Trip Unit memory:

• 

the cause of trip;

• 

the values of currents at time of trip;

• 

the time when the trip operation occurred; and

• 

the total number of times the Trip Unit has tripped the breaker 

electronically, (does not count shunt trip or manual operations) .

If the 120 Vac control power remains available to the Power / Relay 

Module, this information can be viewed by INCOM

®

 / IMPACC

®

 (See 

Section 5 .6) .  Therefore, Users may want to use an uninterruptible 

power supply for the control power to the power relay module .

1.1.3  Discriminator (High Initial Current Release)  

        (For Types LS and LSG Trip Units Only)

When the Digitrip RMS 910 Trip Unit is not equipped with an 

adjustable instantaneous protection setting, i .e . types LS or LSG, a 

DlScriminator circuit (or high initial current release) is provided .  The 

non-adjustable release is pre-set at eleven (11) times the installed 

rating plug current (I

n

) .  The DlScriminator is enabled for approxi-

mately ten (10) cycles following the initial current flow through the 

circuit breaker, provided the load current exceeds approximately 10% 

of the circuit breaker frame (or current sensor) rating .  Whenever 

the load current falls below 10% the discriminator is rearmed .  The 

release, once rearmed will remain enabled until the load current 

passing through the circuit breaker has exceeded the 10% value 

for 10 cycles .  Whenever the DlScriminator trips the circuit breaker, 

the "OVERRIDE / DIS" LED will light "RED", and the Display will read 

"DISC"

 .

In the event the breaker is not intended to trip out on a circuit 

whose current could initially be higher than 11 x I

n

, it is possible to 

make the DlScriminator inactive .
If a circuit breaker would close onto a high short-circuit current, 

when the DlScriminator is inactive, type 

LS

 or 

LSG

 Trip Units will 

rely on the short-time delay function before tripping . If the fault 

current exceeds the short-time withstand current capability of the 

circuit breaker, the OverRlDe protection function will trip the breaker 

without delay (see Section 1 .1 .4) .  Also, please see Section 1 .1 .5 for 

other exceptions when Zone lnterlocking is employed .
The DlScriminator (high initial current release) can be made inactive 

by turning the "

OVERRIDE/

" setting switch (nearest the bottom edge 

of the Trip Unit) from the "

DIS

" position, to the "[blank]" position (see 

Figures 4 and 7) .

otee:

N

This switch has eight (8) positions, and seven (7) of the positions show 

"DIS" in the window, ONLY ONE position shows "[blank]" .

otee:

N

When the "OVERRIDE/"window shows "[blank]", the only fast-acting  

high short-circuit protection available is the OVERRIDE (Fixed  

Instantaneous) (see Section 1 .1 .4 .) .

Содержание Digitrip RMS 910

Страница 1: ...Effective June 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 889B Instructions for Digitrip RMS 910 Trip Unit...

Страница 2: ...3 4 Short Delay Current Setting 18 3 5 Short Delay Time Setting 18 3 6 Instantaneous Current Setting 18 3 7 No Instantaneous Current Setting 19 3 8 Ground Fault Current Setting 19 3 9 Ground Fault Tim...

Страница 3: ...Figure 15 Short Delay Current Settings 16 Figure 16 Short Delay Time Settings 17 Figure 17 Instantaneous Current Settings 17 Figure 18 Ground Fault Current Settings 17 Figure 19 Ground Fault Time Dela...

Страница 4: ...urrent rating of each circuit breaker The Digitrip RMS 910 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 18...

Страница 5: ...on 1 4 will maintain the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 910 Trip Unit can be RESET in two ways Either pres...

Страница 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 9...

Страница 7: ...n Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp...

Страница 8: ...Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 910 Type Ll Figure 4 Digitrip RMS 910 Type LS Figure 5 Digitrip RMS 910 Type LSI F...

Страница 9: ...The non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approxi mately ten 10 cycles following the initial current flow through...

Страница 10: ...ppendix A 1 2 Four Character Information Display Window The four digit alpha numeric display window illustrated in Figures 1 and 2 serves two basic purposes instrumentation and mode of trip and troubl...

Страница 11: ...wer Power Factor and Energy Values 1 2 1 3 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X Power Factor X X X X X X 1 2 1 3 Energy Consumption MWh Rev...

Страница 12: ...lug is missing damaged or not well connected If breaker is closed it will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Pr...

Страница 13: ...l in Figure 1 Note N The peak demand function requires that 120 VAC control power be sup plied to the Power 1 Relay Module The Present Demand is a power value averaged over approximately one second To...

Страница 14: ...elease of the Step push button will initiate a 3 phase waveform capture internally in the Digitrip and in turn calculate all THD and individual values Notice that two Green LEDs THD and IA are now ill...

Страница 15: ...D OR FAILURE OF THE PROTECTION SYSTEM After installing the Rating Plug press and release the TRIP RESET push button to turn off any illuminated LEDs The purpose of the rating plug is to set the value...

Страница 16: ...the long delay current setting Ir for 40 seconds The 40 second delay allows the system to ride through momentary high load conditions and avoid nuisance alarms Long Delay Available Settings Setting 5...

Страница 17: ...gitrip RMS 910 Trip Unit whenever 120 VAC control power is not available to the Power Relay Module see Section 1 4 When a drawout circuit breaker is equipped with a Digitrip RMS 910 Trip Unit it can b...

Страница 18: ...a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM automatically reduces the time to trip to allow for the fact that the load...

Страница 19: ...function does reset rather quickly on the 0 1 second setting for example it will reset in 0 5 second 4 Test Procedures 4 1 General Danger DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUI...

Страница 20: ...al three phase circuit If three phase current had been flowing the Trip Unit would actually have performed correctly Use the APM for correct Trip Unit performance whenever single phase current injecti...

Страница 21: ...the TEST current value will be shown in the display window not the actual current flowing in the breaker 5 Reset the Trip Unit by pressing and releasing the Trip Reset push button see Figure 20 All L...

Страница 22: ...r listed in Section 6 The receiving terminal s can be An Assemblies Electronic Monitor AEM or Breaker Interface Module BIM for local or remote monitoring see Figure 22 and references in Section 6 A re...

Страница 23: ...re daisy chained interconnect shielding but do not ground the connection 1 2 watt carbon resistor required at last breaker See T D 17 513 Breaker Interface Monitor BIM OR 810 Typical IBM or IBM Twiste...

Страница 24: ...button 3 To increment the address press and release the Black DEMAND RESET push button near the display window see Figure 1 The address will increase by one unit each time you press the Black DEMAND...

Страница 25: ...I I View Power Energy Values Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X 1 2 1 3 I I Energy Consumption MWh Reverse Energy Consumption X X X X X...

Страница 26: ...RIP were initiated due to a Short Time Delay over current condition for example the coded message for SDT would be transmitted by the Trip Unit Once the message is received and interpreted by the soft...

Страница 27: ...Reset command remotely from the master computer by the INCOM lMPACC system is exactly equivalent to pressing and releasing the Trip Reset push button on the front of the Trip Unit In addition to the...

Страница 28: ...ker will trip clearing the fault in 0 5 s CASE 2 There is Zone Selective lnterlocking Fault 3 The branch breaker trip unit will initiate the trip in 0 03 s to clear the fault and Z3 will send an inter...

Страница 29: ...View values of phase currents in Display Window see Figure 1 e g 1 50 kA Note N The phase current shown will be that identified by the green LED see Figure 1 that is turned On assume IA It may not be...

Страница 30: ...t Trip Alarm contact Operator Actions 1 Observe the mode of trip LED and the INST message in the Display Window 2 Press and release the STEP push button to view current values IA IB IC and IG or ID in...

Страница 31: ...31 Instruction Leaflet I L 29 889B Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Notes...

Страница 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Отзывы: