Instruction Leaflet 

I. L. 29-889B

Effective June 2011

 Instructions for Digitrip RMS 910 Trip Unit

 

 

eaton corporation

 www.eaton.com

3.7  No Instantaneous Current Setting

For types LS and LSG Trip Units, please see Sections 1 .1 .3 

DlScriminator (High initial Current Release) and 1 .1 .4 OVERRIDE 

(Fixed Instantaneous), for available fast-acting high short-circuit pro-

tection .

3.8  Ground Fault Current Setting

The eight (8) Ground Fault "Pick-up" Current Settings are labeled 

with the code letters "A" through "K" (except there are no "G" or "I" 

settings), as illustrated in Figure 18 .   In general, the specific current 

settings range from 0 .25 to 1 .0 times (I

n

), the rating plug value, but 

cannot exceed 1200 A .  The specific Ground Current Settings for 

each letter are listed in Table 4 and on the (G) Time-Current Curve 

applicable for the circuit breaker (see Section 6) .

otee:

N

For Testing Purposes Only: When using an external single phase current 

source to test low level ground fault current settings, it is advisable to use the 

Auxiliary Power Module (APM) (see Section 1 .6 and Figure 12) .

3.9  Ground Fault Time Delay Setting

As illustrated in Figure 19, there are two different Ground Fault 

curve shapes, i .e ., fixed time (flat) and I

2

t response .  The shape 

selected depends on the type of selective coordination chosen .  The 

I

2

t response will provide a longer time delay in the low-end of the 

ground fault current range than will the flat response .
Five flat ( .I,  .2,  .3,  .4,  .5 sec .) and three I

2

t ( .I*,  .3*,  .5* sec .) 

response time delay settings are available .  The I

2

t response settings 

are identified by the suffix asterisk (*) that appears in the setting 

viewing window .  The I

2

t response is applicable to currents less than 

0 .625 x I

n

, (the I

n

 value is marked on the installed rating plug) .  For 

currents greater than 0 .625 x I

n

, the I

2

t response reverts to the flat 

response .

otee:

N

See also Section 1 .1 .5 on Zone Interlocking .

otee:

N

In addition to the standard Ground Fault protection, the Digitrip RMS 

910 Trip Unit also has a GROUND TIME MEMORY (GTM) function, which 

serves to protect loads in the event of a sputtering arc to ground . Without 

the GTM function, the Trip Unit would normally reset each time the arc sput-

tered, and begin to time-out all over again, so that a sputtering fault may not 

have been detected .  But with the GTM function, the Trip Unit "remembers" 

the sputtering ground current for up to five (5) times the Ground Fault Time 

Setting .  After that time, it does reset automatically .  The GTM function does 

reset rather quickly; on the 0 .1 second setting, for example, it will reset in  

0 .5 second .

4  test procedures

4.1  General

DANGER

DO NOT ATTEMPT TO INSTALL, TEST OR PERFORM MAINTENANCE ON 

EQUIPMENT WHILE IT IS ENERGIZED.  DEATH OR SEVERE PERSONAL 

INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. 

 

DE-ENERGIZE THE CIRCUIT AND DISCONNECT THE CIRCUIT BREAKER 

BEFORE PERFORMING MAINTENANCE OR TESTS. 

 

DO NOT ATTEMPT TO PERFORM DIELECTRIC (OR HIGH POT OR HIGH 

VOLTAGE) WITHSTAND TESTS ON THE CIRCUIT BREAKER WHILE THE 

VOLTAGE DISCONNECT PLUG TO THE POTENTIAL TRANSFORMER MODULE 

IS INSTALLED. (SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR 

SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6).  PTM OR TRIP UNIT 

DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE 

THAN 600 VOLTS. 

 

VERIFY THAT NO VOLTAGE IS PRESENT ON THE CIRCUIT BREAKER BEFORE 

REMOVING THE VOLTAGE DISCONNECT PLUG (SEE FIGURE 11). 

 

REMOVE THE VOLTAGE DISCONNECT PLUG TO ISOLATE THE POTENTIAL 

TRANSFORMER MODULE (FIGURE 11) BEFORE PERFORMING ANY VOLTAGE 

TESTS ON THE CIRCUIT BREAKER.  REINSTALL THE PLUG ONLY AFTER 

ALL VOLTAGE TESTS HAVE BEEN COMPLETED AND CONFIRM THAT NO 

VOLTAGE IS PRESENT ON THE CIRCUIT BREAKER. 

 

REINSTALL THE VOLTAGE DISCONNECT PLUG TO RECONNECT THE 

POTENTIAL TRANSFORMER MODULE BEFORE PLACING THE BREAKER 

BACK INTO SERVICE.  REFER TO THE APPLICABLE CIRCUIT BREAKER 

INSTRUCTION LEAFLET SUPPLEMENT (LISTED IN SECTION 6) FOR 

COMPLETE INSTRUCTIONS.

CAUTION

TESTING A CIRCUIT BREAKER UNDER "TRIP CONDITIONS" WHILE IT IS IN 

SERVICE AND CARRYING LOAD CURRENT, WHETHER DONE BY LOCALLY OR 

BY REMOTE MEANS, IS NOT RECOMMENDED. 

 

ANY TRIPPING OPERATION WILL CAUSE DISRUPTION OF SERVICE 

AND POSSIBLE PERSONAL INJURY RESULTING FROM UNNECESSARY 

SWITCHING OF CONNECTED EQUIPMENT. 

 

TESTING OF A CIRCUIT BREAKER THAT RESULTS IN THE TRIPPING OF THE 

CIRCUIT BREAKER SHOULD BE DONE ONLY WITH THE CIRCUIT BREAKER 

IN THE "TEST" OR "DISCONNECTED" CELL POSITIONS OR WHILE THE 

CIRCUIT BREAKER IS ON A TEST BENCH.

4.2  When To Test

Tests can be conducted with the breaker in the "connected" cell posi-

tion while carrying load current .  However, as stated in the caution 

note in Section 4 .1, good practice will limit circuit breaker in-service 

"trip tests", where required, to maintenance periods during times of 

minimum load conditions .  Testing is accomplished with the breaker 

out of its cell or in the "Test", "Disconnected", or "Withdrawn" (or 

Removed) cell positions .

otee:

N

Since time-current settings are based on desired system coordination 

and protection schemes, the protection settings selected and preset in accor-

dance with Section 3 should not be altered during or as a part of any routine 

test sequence .

Содержание Digitrip RMS 910

Страница 1: ...Effective June 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 889B Instructions for Digitrip RMS 910 Trip Unit...

Страница 2: ...3 4 Short Delay Current Setting 18 3 5 Short Delay Time Setting 18 3 6 Instantaneous Current Setting 18 3 7 No Instantaneous Current Setting 19 3 8 Ground Fault Current Setting 19 3 9 Ground Fault Tim...

Страница 3: ...Figure 15 Short Delay Current Settings 16 Figure 16 Short Delay Time Settings 17 Figure 17 Instantaneous Current Settings 17 Figure 18 Ground Fault Current Settings 17 Figure 19 Ground Fault Time Dela...

Страница 4: ...urrent rating of each circuit breaker The Digitrip RMS 910 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 18...

Страница 5: ...on 1 4 will maintain the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 910 Trip Unit can be RESET in two ways Either pres...

Страница 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 9...

Страница 7: ...n Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp...

Страница 8: ...Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 910 Type Ll Figure 4 Digitrip RMS 910 Type LS Figure 5 Digitrip RMS 910 Type LSI F...

Страница 9: ...The non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approxi mately ten 10 cycles following the initial current flow through...

Страница 10: ...ppendix A 1 2 Four Character Information Display Window The four digit alpha numeric display window illustrated in Figures 1 and 2 serves two basic purposes instrumentation and mode of trip and troubl...

Страница 11: ...wer Power Factor and Energy Values 1 2 1 3 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X Power Factor X X X X X X 1 2 1 3 Energy Consumption MWh Rev...

Страница 12: ...lug is missing damaged or not well connected If breaker is closed it will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Pr...

Страница 13: ...l in Figure 1 Note N The peak demand function requires that 120 VAC control power be sup plied to the Power 1 Relay Module The Present Demand is a power value averaged over approximately one second To...

Страница 14: ...elease of the Step push button will initiate a 3 phase waveform capture internally in the Digitrip and in turn calculate all THD and individual values Notice that two Green LEDs THD and IA are now ill...

Страница 15: ...D OR FAILURE OF THE PROTECTION SYSTEM After installing the Rating Plug press and release the TRIP RESET push button to turn off any illuminated LEDs The purpose of the rating plug is to set the value...

Страница 16: ...the long delay current setting Ir for 40 seconds The 40 second delay allows the system to ride through momentary high load conditions and avoid nuisance alarms Long Delay Available Settings Setting 5...

Страница 17: ...gitrip RMS 910 Trip Unit whenever 120 VAC control power is not available to the Power Relay Module see Section 1 4 When a drawout circuit breaker is equipped with a Digitrip RMS 910 Trip Unit it can b...

Страница 18: ...a breaker is re closed soon after a Long Delay Trip and the current again exceeds the Long Delay Current Setting Ir the LTM automatically reduces the time to trip to allow for the fact that the load...

Страница 19: ...function does reset rather quickly on the 0 1 second setting for example it will reset in 0 5 second 4 Test Procedures 4 1 General Danger DO NOT ATTEMPT TO INSTALL TEST OR PERFORM MAINTENANCE ON EQUI...

Страница 20: ...al three phase circuit If three phase current had been flowing the Trip Unit would actually have performed correctly Use the APM for correct Trip Unit performance whenever single phase current injecti...

Страница 21: ...the TEST current value will be shown in the display window not the actual current flowing in the breaker 5 Reset the Trip Unit by pressing and releasing the Trip Reset push button see Figure 20 All L...

Страница 22: ...r listed in Section 6 The receiving terminal s can be An Assemblies Electronic Monitor AEM or Breaker Interface Module BIM for local or remote monitoring see Figure 22 and references in Section 6 A re...

Страница 23: ...re daisy chained interconnect shielding but do not ground the connection 1 2 watt carbon resistor required at last breaker See T D 17 513 Breaker Interface Monitor BIM OR 810 Typical IBM or IBM Twiste...

Страница 24: ...button 3 To increment the address press and release the Black DEMAND RESET push button near the display window see Figure 1 The address will increase by one unit each time you press the Black DEMAND...

Страница 25: ...I I View Power Energy Values Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X 1 2 1 3 I I Energy Consumption MWh Reverse Energy Consumption X X X X X...

Страница 26: ...RIP were initiated due to a Short Time Delay over current condition for example the coded message for SDT would be transmitted by the Trip Unit Once the message is received and interpreted by the soft...

Страница 27: ...Reset command remotely from the master computer by the INCOM lMPACC system is exactly equivalent to pressing and releasing the Trip Reset push button on the front of the Trip Unit In addition to the...

Страница 28: ...ker will trip clearing the fault in 0 5 s CASE 2 There is Zone Selective lnterlocking Fault 3 The branch breaker trip unit will initiate the trip in 0 03 s to clear the fault and Z3 will send an inter...

Страница 29: ...View values of phase currents in Display Window see Figure 1 e g 1 50 kA Note N The phase current shown will be that identified by the green LED see Figure 1 that is turned On assume IA It may not be...

Страница 30: ...t Trip Alarm contact Operator Actions 1 Observe the mode of trip LED and the INST message in the Display Window 2 Press and release the STEP push button to view current values IA IB IC and IG or ID in...

Страница 31: ...31 Instruction Leaflet I L 29 889B Effective June 2011 Instructions for Digitrip RMS 910Trip Unit eaton corporation www eaton com Notes...

Страница 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Отзывы: