3 Installation
3.4 IP66 / NEMA4X degree of protection
54
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
3.4 IP66 / NEMA4X degree of protection
IP66 DC1-S… variable frequency drives are available in two versions:
•
DC1-S…-A66N: Activation via control signal terminals
•
DC1-S…-A6SN: Controlled with controls on the front and/or control
signal terminals
Figure 28: IP66 variants
The units must be mounted, with four screws and in a vertical position, on a
wall or panel that is made of nonflammable material and is stable enough to
hold the variable frequency drive’s weight.
On the DC1-S…-A6SN version, the main disconnect switch can be locked in
the OFF position with a standard padlock.
DC1-S…-A66N
DC1-S…-A6SN
Figure 29: Openings for fixing
screws
PWR
OFF
ON
REV
FWD
0
= 4 x M4
1 Nm
(8.85 lb-in)
FS1, FS2
Figure 30: DC1-S…-A6SN with
padlock
▶
Push on the center of
the switch in order to
open the opening for
the padlock.
PWR
OFF
ON
REV
FWD
0
ON
OFF
PWR
⌀ = 5 mm → 2 x
(⌀ = 0.20"
→
2 x)
⌀