IQ DP-4000
SECTION 5 - PROGRAMMING THE IQ DP-4000
5. 9. 1 Power Demand, Fixed/Sliding
The IQ DP-4000 is programmed for the power related
demand to correspond to either a fixed or sliding
window.
•
Fixed Power Demand. With a fixed demand
window, the demand calculation is based on, and
updated at, the user-selected time interval. For
example, if you select a 1 5-minute demand window,
a new demand will compute every 1 5 minutes,
based on the energy used during the last 1 5
minutes.
•
Sliding Power Demand. For a sliding window, the
demand calculation is based on the user-selected
interval time, and is updated every minute. For
example, if you select a 1 5-minute demand window,
the calculated demand is based upon the previous
1 5 minutes, but is updated every minute.
Set the power related demand by using
SW4 No. 2.
Place the switch in the:
•
OFF position for the sliding power demand window
•
ON position for the fixed power demand window
5.9.2 Power Demand Time Interval
Switch
SW4 Nos. 3, 4, and 5
determine the time
interval, in minutes, that the consumption sampling for
the power related demand calculations are based. Table
5.G shows the settings for selecting the power demand
interval.
•= OFF
Q
= ON
= Not Applicable
Table 5.G Power Demand Intervals for Watts, Vars
and VA
TD1 7548A
5. 9. 3 Current Demand Time Interval
Switch
SW4 Nos. 6, 7,
and
8
determine the time
interval, in minutes, that the consumption sampling for
the current related demand calculations are based.
Table 5.H shows the settings for selecting the current
demand time intervals.
•= OFF
Q
= ON
Table 5. H Demand Sampling Interval for lA, Is, and lc
5.1 0 ENERGY SETPOINTS
5. 10. 1 Reset Energy from Faceplate Setpoint
This setpoint enables or prevents you from resetting the
energy values (Watt-hours, Var-hours, and VA-hours)
from the faceplate. Set Switch
SW5 No. 1
in the:
•
OFF position to prevent resetting an energy value
from the faceplate
•
ON position to enable resetting at the faceplate. To
reset an energy value from the faceplate, you select
the parameter (Metered Watt-hours, Var-hours, or
VA-hours), and then hold down the Reset button
until the value is 0.
5. 10. 2 Energy Resolution
The IQ DP-4000 can be programmed to display energy
readings in KILO or MEGA energy units. A single switch
SW5 No. 2
sets the energy resolution. The energy value
rolls-over to zeros when it exceeds 999999.
Set switch
SW5 No. 2
in the:
•
OFF position for KILO energy units
•
ON position for MEGA energy units
25