![Eaton Cutler-Hammer IQ DP-4000 Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/eaton/cutler-hammer-iq-dp-4000/cutler-hammer-iq-dp-4000_installation-operation-and-maintenance-instructions_3743627010.webp)
IQ DP-4000
SECTION 2 - HARDWARE DESCRIPTION
2.2.3 Metering Specifications
Table 2.C shows the metering specifications for the IQ
DP-4000.
Displayed
I
tem
through
IMPACC
Local
Display
AC Amperes Phases
+1-
0.3%
+1-
0.3%
+1-
1 digit
A, 8,C
AC Voltage
+1-
0.3%
+1-
0.3%
+1-
1 digit
Phase A-8, 8-C, C-A
+1-
0.3%
+1-
0.3%
+1-
1 digit
Phase A-N, 8-N, C-N
Watts
+1-
0.6%
+1-
0.6%
+1-
1 digit
Vars
+1-
0.6%
+1-
0.6%
+1-
1 digit
VA
+1-
0.6%
+1-
0.6%
+1-
1 digit
Watt-hours
+1-
0.6%
+1-
0.6%
+1-
1 digit
Var-hours
+1-
0.6%
+1-
0.6%
+1-
1 digit
VA-hours
+1-
0.6%
+1-
0.6%
+1-
1 digit
Power Factor
+I-
1 %
+I-
1 %
Frequency
+1-
0 . 1 Hz
+1-
0.1 Hz
%THO
Through 3 1 st Harmonic
Table 2.C Metering Specifications
Accuracy is maintained from 3% to 250% of the full
scale of the device.
Nominal Full Scale Current:
5
Amps ac
Nominal Full Scale Voltage:
120-600
Vac
Certification
UL:
Listed UL-508, File
E6279 1 ,
NKCR Auxiliary Devices
NEMA:
3R,
12
(when gasketed)
FCC:
Part
15,
Class A
TD1 7548A
7
www
. ElectricalPartManuals
. com