SECTION 4 - INSTALLATION AND STARTUP
'W1th CoMMunico.tion Moclule
5.400
0 50
-j
4.420
DO
Figure 4.2 Side Profile Depth Dimensions
4.3 MOUNTING THE POWER SUPPLY MODULE
SEPARATELY (OPTIONAL)
The IQ DP-4000 uses one of two power modules, a 3-
Phase power module or a separate source power supply
module:
•
A 3-Phase power module (Models 4030 and 41 30)
receives its power from the same source it monitors.
The advantage is that the IQ DP-4000 does not need
a separate power source to run.
•
The IQ DP-4000, equipped with a separate source
power supply module (Models 401 0 and 41 1 0),
receives power from a source other than the one it
monitors. The advantage to this style is that if there
is a loss of power to the monitored system, the IQ
DP-4000 will not lose power. You may mount either
power module separately from the chassis. If you do,
check that:
•
The location allows for a cable connection
between the IQ DP-4000 chassis and the
TD1 7548A
power module using either the 36 in. (91 .4
em) or the 45 in. (1 1 4.25 em) Extension
Cable Option
•
The separated power module can physically
fit in the desired location (See clearance
dimensions in Figure 4.3)
•
To separate the power module from the IQ DP-4000,
remove the two screws that secure it to the IQ DP-
4000. Use the power module as a drilling template at
the new location. Remount it in the properly drilled
and tapped holes, using the two 8-32 screws .
I
'
I
I
6.750
'
!
4.550
I
!
I
. ?00
'
I
2.060
3.200
0
I
� �
'
!
Figure 4.3 Power Module Dimensions
4.4 WIRING
When you wire the IQ DP-4000, you must follow a
suitable wiring plan drawing. A wiring plan, created either
by you or your OEM, describes all electrical connections
between the IQ DP-4000 and the machine or process
equipment. All wiring must conform to applicable federal,
state, and local codes.