![Eaton Cutler-Hammer Easy-Start ES Series Скачать руководство пользователя страница 79](http://html1.mh-extra.com/html/eaton/cutler-hammer-easy-start-es-series/cutler-hammer-easy-start-es-series_instruction-manual_3854391079.webp)
Easy-Start ES Instruction Manual
Options
SECTION 4
4-8
Available Options
Special Functions
Cutler-Hammer ÒIQ Data Plus IIÓ Monitoring
Device, catalog suffix ÒQ8Ó, provides the following
readings:
AC Ampere
Phase A
Phase B
Phase C
AC Voltage
Phase A-B Phase A-Neutral
Phase B-C Phase B-Neutral
Phase C-A Phase C-Neutral
Megawatts
Megavars
Power Factor
Frequency
Megawatt Demand
The IQ Data Plus II is offered as a monitoring
device only and all protective functions are
disabled, or set so they do not race with Easy-
Start ES protective functions.
The following CTÕs are supplied with the IQ Data
Plus:
Easy-Start ES Cat. No.
CT
ES045, ES070
Three 100:5 CTÕs
ES120
Three 200:5 CTÕs
ES180, ES250, ES260
Three 300:5 CTÕs
ES360
Three 500:5 CTÕs
ES500, ES560
Three 800:5 CTÕs
ES750, ES950
Three 1000:5 CTÕs
Notice
- IQ Data Plus II Ampere Display
Range:
Minimum: 2% of CT used with IQ
Maximum: 500% of Easy-Start ES Maximum
Ampere Rating
If local codes or customer preference prohibit line
voltage on the door, do not use this option.
Cutler-Hammer ÒIQ DataÓ Monitoring Device,
catalog suffix ÒQ7Ó, provides the following
readings:
AC Ampere
Phase A
Phase B
Phase C
AC Voltage (Motor)
Phase A-B
Phase B-C
Phase C-A
The following CTÕs are supplied with the IQ Data:
Easy-Start ES Cat. No.
CT
ES045, ES070
Three 100:5 CTÕs
ES120
Three 200:5 CTÕs
ES180, ES250,
Three 300:5 CTÕs
ES260, ES360
ES500, ES560
Three 800:5 CTÕs
ES750, ES950
Three 1000:5 CTÕs
Notice
- IQ Data Ampere Display Range:
Minimum: 2% of CT used with IQ
Maximum: 500% of Easy-Start ES Maximum
Ampere Rating
If local codes or customer preference prohibit line
voltage on the door, do not use this option.
StockCheck.com