Easy-Start ES Instruction Manual
Troubleshooting
SECTION 5
5-12
J4 PIN #
FUNCTION
LOCATION
CONDITION
TEST VOLTAGE
1
+10VDC
VR1-2
3-PH VOLTAGE ON
10V +.5
2
CURRENT SIG
TP1
START
0 TO 4.5 VDC
CURRENT SIG
TP1
RUN/AT FULL LOAD
0.90V + .04 VDC
3
TRIGGER VOLTS
TP6
RUN FULL LOAD
6 TO 8 VDC
RUN NO LOAD
3 TO 3.5 VDC
4
CURR SIG
03 COLL
START
0
CURR SIG
03 COLL
RUN
0.1 TO .9 VDC
5
CURR TRIP V
U7-11
START
0 TO 7 VDC
RUN NO LOAD
0 TO 1 VDC
6
SPARE
7
END OF RAMP
R253
START
0
END OF RAMP
R253
RUN
10V +2 VDC
8
RAMP V
Z5 CATHODE
START
0 TO 6.8 VDC
RAMP V
Z5 CATHODE
RUN/STOP
0
9
TRIP LINE
D44 CATHODE
FAULT TRIP
8V +2 VDC
10
LOAD SENSE
U2-1
START
0
LOAD SENSE
U2-1
RUN F LOAD ES-ON
-3.1 TO -3.7 VDC
11
INV INPUT
U2-6
START/RUN/STOP
INPUT ONLY
12
NON-INV INPUT
TP5
START
0 TO 2.5 VDC
NON-INV INPUT
TP5
RUN
1 V +.2 VDC
13
+12C
TP8
START
11V +1V
+12C
TP8
RUN/STOP
0
14
+12A
TB1-2
START/RUN/STOP
12V +.5
15
+12B
TP12
START/RUN
12V +.8
+12B
TP12
STOP
0
16
+12D
TP13
STOP
12V PULSE
17
STOP SIG
D45 ANODE
STOP
0-6V RAMP PULSE
18
LOCKOUT
TP14
START/RUN
+10V +.8V
LOCKOUT
TP14
STOP
0
19,20,21
SPARES
22
AUX +12B
+12V +.9V
23
AUX +12A
+12V +1V
24
-12A
VR3-3
START/RUN/STOP
-12V +.5 VDC
25
LOGIC GROUND
TB1-1
SCR Diagnostic Tests
J4 Connector Test Voltages
Table 5-1