![Eaton Cutler-Hammer Easy-Start ES Series Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/eaton/cutler-hammer-easy-start-es-series/cutler-hammer-easy-start-es-series_instruction-manual_3854391076.webp)
Available Options
Circuit Breakers
Thermal-Magnetic Breaker
Table 4-1
(1) All ratings shown above for HFD type can be used with either ES045 or ES070 models. Magnetic
trip adjust is not available on HFD type. Magnetic trip is set at approximately 10 times the circuit
breaker trip rating.
(2) All ratings shown above for HKD type can be used with either ES180, 250 or ES260 models.
(3) Adjustable rating plug 400-800 Amps.
(4) Adjustable rating plug 600-1200 Amps.
(5) When adjustable rating plugs are used, short delay pickup (magnetic) settings track the selected
position of the adjustable rating plug. For example, with an adjustable 800 amp rating plug set at
50%, and the short delay pickup (magnetic) set at 4X, the short delay pickup is 800 x 50% x
4=1600 amps.
Easy-Start ES Instruction Manual
Options
SECTION 4
4-5
Option No.
With
Mag.
Nominal HP
Thermal
Shunt
Easy-Start
Frame
Breaker
Trip
Magnetic
Trip
ES Model
Size
Type
Amps
Adj.
208
460
230V
575V
C01
C30
ES045(1)
F
HFD
30
(1)---
5
15
C02
C31
ES045(1)
F
HFD
60
(1)---
15
30
C03
C32
ES070(1)
F
HFD
100
(1)---
20
40
C22
C51
ES070(1)
F
HFD
150
(1)---
25
50
C04
C33
ES120
J
HJD
150
5X-10X
25
50
C05
C34
ES120
J
HJD
200
5X-10X
40
75
C06
C35
ES120
J
HJD
250
5X-10X
50
100
C07
C36
ES180(2)
K
HKD
200
5X-10X
40
75
C08
C37
ES180(2)
K
HKD
250
5X-10X
50
100
C09
C38
ES180(2)
K
HKD
300
5X-10X
75
150
C10
C39
ES250(2)
K
HKD
400
5X-10X
100
200
C10
C39
ES260(2)
K
HKD
400
5X-10X
100
200
C11
C40
ES360
MC
HMC
800 (3)
3X-10X (5)
150
300
C11
C40
ES500
MC
HMC
800 (3)
3X-10X (5)
200
450
C11
C40
ES560
MC
HMC
800 (3)
3X-10X (5)
200
450
C12
C41
ES750
NC
HNC
1200 (4)
2X-8X (5)
300
600
C13
C42
ES950
NC
HNC
1200 (4)
2X-8X (5)
400
800