32
Manual CEAG CG-Controller for CG 2000/ZB-S
30080001458 (C) July 2016 www.ceag.de
10 CG-Controller configuration created from PC software
10 CG-Controller configuration created from
PC software
After a SD is inserted, the address 0x060 inconfigcg.dat is tested.
If the CG-Controller detects a new CG-Controller configuration for the
PC software, the place is 0x01.
If confirmed with yes, the new configuration will be accepted as follows:
Line
Display:
1
New CG controller
2
Accept configuration of
3
SD
n/y
4
Operation:
Menu One menu level higher
/
Select yes/no
Confirm selection
10.1 Read new configcg.dat from SD automatically
Line
Display:
1
New configuration
2
Load ...
3
Read configcg.dat..
4
Please wait...
10.2 Find devices automatically
Line
Display:
1
2
Automatic search
3
· · · · ·
4
Please wait...
10.3 Save Configcg.dat to SD
Line
Display:
1
New configuration
2
Save....
3
Save configcg.dat
4
Please wait...
At the end Byte EE_NewConfigCG at 0x060 is setted to 0xFF.
10 .3 .1 Network device configuration created
from PC software
First the system performs the steps described under «10 CG-Controller
configuration created from PC software». The PC software sets the
address 0x060 in configcg.dat on 0x01 if devices have been deleted
or added.
After that the device status of all network systems is tested. If the
device status of a system = 0x02, configxx.dat and textexx.dat will
automatically be downloaded to this system. All systems marked
with 0x02 on the SD will be updated. Finally the CG-Controller sets
0x060 on 0xFF and the particular device status on 0x01.