22
Manual CEAG CG-Controller for CG 2000/ZB-S
30080001458 (C) July 2016 www.ceag.de
9 Menus
9 .8 .3 Next FT
If you exit the menu item with Menu or
, the new data (time and
date, for example 14:15 13.09.2002) of the next functiontest will
be transferred to the emergency lighting system in the next step.
9 .8 .3 .1 Next FT safety function
The new time for the next function test will be sent to all devices
that are present. You can use this safety function, however, to
transfer time “Next FT” + 1 hour. After that, 15:15 20.09.2002
will appear in the menu item «Basic settings
→
Functiontest» in the
connected devices.
However, the CG -Controller will perform the next function test on
all devices on 20.09.2002 at 14:15. If the CG-Controller happens to
be out of operation, the emergency lighting systems will automa-
tically perform the next function test on 20.09.2002 at 15:15 as a
safety function.
Line
Selection (submenu)
1
Select language
2
Setup time and date
3
Next functiontest
∕
4
Next durationtest
5
Relay settings
6
etc.
Line
Display:
1
Next FT
2
14:15
13.09.2002
3
Change
4
Interval in days:
007
Operation:
Menu Accept and
one menu level higher
/
Insertion pointer
(cursor) left/right
/
Reduce/increase value
Setting range 1 ... 365
Default value: 7 days
Accept and
one menu level higher
1
Start all devices
2
Prg. next FT
3
Device
=
01
4
Please wait
9 .8 .4 Next BT
If you exit the menu item with Menu or
, the new data (time and
date, for example 14:15 13.09.2002) of the next function test will
be transferred to the emergency lighting system in the next step.
9 .8 .4 .1 Next DT safety function
The new time for the next durationtest will be sent to all devices that
are present. You can use this safety function, however, to transfer
time “Next DT” + 1 hour. After that, 15:15 13.08.02 will appear in the
menu item «Basic settings
→
Durationtest» in the connected devices.
However, the CG-Controller will perform the next durationtest on all
devices on 13.08.02 at 14:15. If the CG-Controller happens to be out
of operation, the emergency lighting systems will automatically per-
form the next durationtest on 13.08.02 at 15:15 as a safety function.
Line
Display:
1
Next BT
2
14:15
13.09.2002
3
Change
4
Interval in mon.:
11
Operation:
Menu Accept and
one menu level higher
/
Insertion pointer (cursor)
left/right
/
Reduce/increase value
Setting range 1 ... 12
Default value: 12 months
Accept and one menu level
higher
1
Start all devices
2
Prg. next BT
3
Device
=
01
4
Please wait
Line
Selection (submenu)
1
Select language
2
Setup time and date
3
Next functiontest
4
Next durationtest
5
Relay settings
6
etc.