27
Manual CEAG CG-Controller for CG 2000/ZB-S
30080001458 (C) July 2016 www.ceag.de
9 Menus
A precondition for searching for emergency lighting systems is
that on the emergency lighting system in the menu item «Basic
settings» -> «Connection to the » a device address must have
been set to greater than zero and must be unique. A device
address may only be assigned once on the network of all emer-
gency lighting systems.
Line
Selection (submenu)
1
Find devices autom.
2
Manually add/delete
∕
3
Synchronize clock
9 .9 .2 Adding/deleting manually
(device type=CG2000/ZB-S)
9 .9 .2 .1 Device already present
9 .9 .2 .2 Device not yet present
First, in Line 1, in the ”No.:“ input box, select the system num-
ber. After that, select ”Add manually = yes“ in Line 2.
This follows by input of the NID.
After entering the NID and ENTER the device name is displayed
in line 4. If the wrong NID has been entered, communication
failure is displayed in line 4.
Line
Display:
1
Device address:
01
↔
2
Address is
assigned
↔
3
ID=
12 34 56 78 12 34
4
Device name
Operation:
Menu One menu level higher
/
Change
Previous input field
Next input field
Line
Display:
1
Device address:
01
↔
2
Address is
free
↔
3
ID=
00 00 00 00 00 00
4
Device name
Line
Display:
1
Device address:
01
↔
2
Add manually.
n/y
3
ID=
00 00 00 00 00 00
4
Line
Display:
1
Device address:
01
↔
2
3
ID=
01 00 00 00 00 00
4
Device name
Operation:
Menu One menu level higher
/
Select byte
/
Change byte
Confirm selection
Operation:
Menu One menu level higher
/
Change
Previous input field
Next input field
Operation:
Menu One menu level higher
/
Change type
Previous input field
Switch to ID input
9 .9 .1 .5 Error analysis for Finding device autom .
If you are working on the emergency lighting system with the
Lonmaker, for example, the domain may be out of adjustment in
some cases.
For the CG-Controller to search for emergency lighting systems,
the domain length must be equal to zero (standard delivery confi-
guration of CG 2000 emergency systems). If the domain of your
emergency lighting system needs to be reinitialised, please con-
tact the CEAG plant customer service department.