Access Power Solutions Installation Guide (APS3-400 Series)
24
Copyright © 2007-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-52D July 2010
Step 2 - Terminate the cabling
•
Connect only voltage-free switch or relay contacts to Digital Inputs.
•
Do not exceed the voltage and current limits of the relay contacts.
•
For wire size and I/O ratings see Specifications on page
.
1
Route the cabling through the access hole in the Input/Output cover to the
terminal blocks on the I/O board.
2
Test the insulation and continuity of the cabling.
3
Terminate the wires into the push-connect terminals (see following diagram).
4
Replace the I/O board.
"
Input/Output (I/O) cover.
#
I/O board.
$
Digital input terminals (push-connect type).
%
Alarm relay (digital output) terminals (push-
connect type).
Step 3 - Replace the cover and secure cables
1
Replace the Input/Output (I/O) cover.
2
Use cable ties to secure the cable(s) and prevent strain on the connections.
Step 4 - Set up SC200 or SC100
Configure the inputs and outputs after completing the installation and all the Startup
Tasks on page
.
For configuration details see Digital Inputs and Digital Outputs in the System
Controller Operation Handbook. For details about setting up and testing see
Input/Output (I/O) in the System Controller Operation Handbook.