Installation
Copyright © 2007-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-52D July 2010
25
Step 5 - Connect SiteSure-3G input/output module(s), if required (SC200 only)
If additional input/outputs are required then connect SiteSure-3G modules to the dc
power system. A SiteSure-3G input/output module has the following features:
Digital
Inputs
10
Digital Outputs (relays)
6
Analog Inputs (-10V to +10V)
4
Current Sense Inputs
3
Temperature
Sense
Inputs
2
Bus Voltage Input (0-60V)
1
1
Route CAT 3 patch cable (4 pair, 26AWG, UTP, 75°C) from the SiteSure-3G
module to the rear of the dc power system.
2
Terminate the cable with RJ45 plugs.
3
Test the insulation and continuity of the conductors.
4
Connect the cable to a spare RJ45 socket (S1, S2 or S3) on the Voltage Feed
Module board (see following diagram).
If additional SiteSure-3G input/output modules are to be connected then use an
RJ45 splitter.
5
Use cable ties to secure the cable and prevent strain on the connectors.
6
Connect the cable to socket YH11 on the SiteSure-3G module.
7
Replace the APS covers.
For details on setup refer to the SiteSure-3G Installation Guide. See Related
Information on page
"
Voltage feed module
#
RJ45 sockets (S1, S2 and S3)