Appendix C
Specifications
Copyright © 2007-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-52D July 2010
71
A
p
p
e
n
d
i
x
C
Specifications
Certifications
Electrical Safety
UL 60950-1
System Input
Input Voltage
120V, 208-240V (nominal)
1W + N + PE (120V nom.):
36A
2W + PE (208-240V nom.):
36A/ph
3 x cord with IEC plugs,
1W + N + PE (120V nom.):
3 x 12A
Input Current Rating (maximum)
3 x cord with IEC plugs,
2W + PE (208-240V nom.):
3 x 12A
Frequency 50-60Hz
AC wire size
Conduit
wiring:
IEC plug cords:
8 AWG See details on page
14 AWG See details on page
Maximum Ground Leakage Current
1.3mA per rectifier
System Output
Output Voltage (nominal)
48V
Output Voltage
Range
Preset
Voltage
43 - 58V
54.5V ± 0.1V
Total Output (maximum)
APR48-ES rectifiers
120V ac:
208-240V ac:
3.6kW/75A max. (43-58V)
6.0kW/125A max.
APR48-3G rectifiers
120V ac:
208-240V ac:
3.3kW/68.7A max. (43-58V)
5.4kW/112.5A max.
Load Output (maximum)
APR48-ES rectifiers
120V ac:
208-240V ac:
2.4kW/50A
4.0kW/83.3A
APR48-3G rectifiers
120V ac:
208-240V ac:
2.2kW/45.8A
3.6kW/75A
Recharge Output (maximum)
APR48-ES rectifiers
120V ac:
208-240V ac:
1.2kW/25A
2.0kW/41.7A
APR48-3G rectifiers
120V ac:
208-240V ac:
1.1kW/22.9A
1.8kW/37.5A