Installation
Copyright © 2007-2010 Eaton Corporation. All Rights Reserved.
IPN 997-00012-52D July 2010
27
Battery CB
Rating
Cable size
(Note 1)
2-hole Crimp Lug
(¼" studs, 5/8" spacing)
(Note 2)
Crimping tool
(Note 2)
100A
1
AWG
120A
1
AWG
YA1CL-2TC14 Y1MR
Notes:
1
Minimum cable size. Does not allow for excessive voltage drop in long cable runs at high
current.
2
Part numbers are for FCI-BURNDY® products. In US/Canada use these parts or equivalent
UL-listed crimp lugs.
Step 2 - Connect load cables
1
Select load cable to suit the load circuit breaker (refer to following table).
2
Route the load cables to the APS.
3
Terminate the load live and common cable(s) with suitable crimp lugs (refer to
the following table).
4
Connect the load common cable(s) on the common bar at the load termination
points.
5
Terminate the load live cable(s) at the load circuit breaker terminal(s).
6
Tighten all terminations to 3.9 - 4.5Nm (35 - 39 inch-pounds).
Load CB
Rating
(Note 1)
Cable size
(Note 2)
2-hole Crimp Lug
(¼" studs, 5/8" spacing)
(Note 3)
Crimping tool
(Note 3)
5-15A
14
AWG
20A
12
AWG
25-30A
10
AWG
YAV10-2TC14 Y8MRB-1
40A
8
AWG
YA8CL-2TC14
50A
6
AWG
YA6CL-2TC14
60A
4
AWG
YA4CL-2TC14
80A
3
AWG
(Note 4)
YA3CL-2TC14
100A
1
AWG
YA1CL-2TC14
Y1MRTC
Notes:
1
See load circuit breaker derating factors on page
2
Minimum cable size. Does not allow for excessive voltage drop in long cable runs at high
current.
3
Part numbers are for FCI-BURNDY® products. In US/Canada use these parts or equivalent
UL-listed crimp lugs.
4
If 3 AWG cable is not available use 2 AWG cable and YA2CL-2TC14 crimp lug (Y1MRTC
crimping tool).