10.2.6 Restarting a Single UPM
1.
On UPM, close CB1.
2.
Observe UPM monitor screen becoming active as an indication of logic power.
3.
Verify UPM is shown on the SBM mimic screen.
4.
On UPM, set
BATTERY
switch to
NORMAL
.
5.
On UPM, set
MODE
switch to
NORMAL
.
6.
On UPM, turn the
START
switch to the right for 2 seconds and then release.
7.
When UPM Battery Disconnected alarm and notification is received, close UPM
battery disconnect breaker.
8.
UPM, will automatically return to on line condition.
The rectifier turns on, then the inverter turns on. When the inverter reaches full
voltage, K3 closes. Logic power is supplied and the UPM is ready to supply power to
the critical load. It takes less than 1 minute for the UPM to achieve Normal mode.
9.
On SBM mimic screen, check for presence of UPM.
10.2.7 Using the UPM LOAD OFF Pushbutton
NOTE:
The UPM
LOAD OFF
pushbutton will only interrupt the ability for that module
to deliver power to the critical bus. The redundant modules will continue to
support the critical load
.
To remove all power from the critical load, use the
SBM EMERGENCY UPM OFF pushbutton.
Load Off is initiated by the covered, red UPM
LOAD OFF
pushbutton on the
Monitor Panel. This pushbutton is protected by a clear plastic shield to prevent
accidental activation. In an emergency, you can press this pushbutton to
instantaneously open the input breaker and interrupt UPM output. The UPM
remains locked off until you reset the
LOAD OFF
pushbutton.
WARNING
All power to the critical load is lost when you press this
pushbutton. Use this feature only in an emergency or when you
want to immediately de-energize the critical load.
To restart the UPS after pressing the
LOAD OFF
pushbutton, follow the procedure
Resetting the UPM after Load Off" of this chapter before starting the UPS.
NOTE:
The UPM Remote Emergency Load Off option functions the same way as the
LOAD OFF pushbutton on the Monitor Panel.