DESCRIPTION:
DRAWING NO:
3 of 3
SHEET:
ONELINE DRAWINGS OF PARALLEL
CAPACITY/REDUNDANT SYSTEM
164201150−4
A−14
EATON
Powerware 9315 Parallel Capacity/Redundant System
164201150 Rev. E
www.powerware.com
NOTE:
1. Accommodates one to eight UPMs. Four UPM system shown.
NOTE:
2. A bypass neutral feeder must be installed when the output neutral is used. If no
bypass neutral is installed, the output neutral is to be bonded to the chassis in the
SBM through the minimum size copper conductor listed in Table I. In either case, fully
rated neutral conductors are to be run from the output of each UPM to the neutral
buss bar inside the SBM.
Table I.
Minimum Size Copper Bonding Jumper
SBM Model
Wire Size (kcmil)
1200A
250
1600A
300
2000A
400
2500A
500
3000A
600
4000A
700