REMOTE EMERGENCY POWER OFF
1 of 2
A−54
EATON
Powerware 9315 Parallel Capacity/Redundant System
164201150 Rev. E
www.powerware.com
1.
The Remote EPO feature shuts down the UPS modules, opens all breakers in the System
Bypass Module and isolates power from your critical load. Local electrical codes may also
require tripping upstream protective devices to the UPS modules.
2.
To open all UPM breakers, a separate twisted pair of wires and an EPO Kit (sold
separately) must be installed to the modules from the SBM.
3.
Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control
wiring in separate conduit from the power wiring. The wire should be rated at 24 volts,
1 amp minimum.
4.
Refer to Table P of this drawing and to applicable chapters for information about installing
control remote EPO.
5.
Refer to drawings 164201150−5 and 164201150−9 for location of the Customer Interface
panel and drawing 164201150−14 for terminal block location on the Customer Interface
Panel.
Table P. Remote EPO
1
2
REMOTE
EPO
SWITCH
TWISTED
WIRES (2)
TB2
Remote EPO switch rating is 24 VDC.
1 amp minimum if supplied by user.
NOTE:
This switch must be a dedicated switch, and not
tied into any other circuits.