7.3.2
Redundant CBP Mode (Optional)
The Parallel Capacity/Redundant system can be protected against failure of the
CBP breaker to close if an electrically interlocked System Maintenance Bypass
(SMB) with Redundant CBP controls has been provided. The Redundant CBP
controls protect the critical load against power losses caused by CBP close failures
during manual or automatic operations.
Redundant CBP operations can be recognized by an alarm condition at the SBM
and the following breaker conditions:
CBP
OPEN
CBS
OPEN
FBP
OPEN
MIS
CLOSED
MBP
CLOSED
CAUTION
The critical load is not protected while the Parallel/ Capacity
system is in Maintenance Bypass or Bypass mode.
Once Redundant CBP operation has occurred, the SBM must be isolated to allow
CBP breaker maintenance without impact on the system’s critical load. To achieve
SBM isolation, the Redundant CBP controls have been interlocked with the System
Maintenance Bypass controls. To exit from Redundant CBP operation, the SMB
control switch must be turned to the
TO MAINT
position. This action opens the
UPS system MIS breaker and places the the UPS system fully into Maintenance
Bypass mode.
After the CBP breaker has been repaired, the UPS system can be transferred from
Maintenance Bypass mode to Bypass mode as described above.
Figure 7−5 shows the path of electrical power through the Parallel
Capacity/Redundant system when operating in Maintenance Bypass mode.