DESCRIPTION:
DRAWING NO:
SHEET:
SBM CUSTOMER INTERFACE PANEL
6 of 7
164201150−13
A−45
EATON
Powerware 9315 Parallel Capacity/Redundant System
164201150 Rev. E
www.powerware.com
Table K. Customer Interface Panel Inputs and Outputs (Cont’d)
Terminal
Block
TB Pin #
Name
Description
TB4
1
ON UPS
Contacts used to indicate On UPS status of
Parallel Capacity/Redundant System
2
ON UPS RTN
3
ON BYPASS
Contacts used to indicate On Bypass status
of Parallel Capacity/Redundant System
4
ON BYPASS RTN
5
RELAY # 1 NC
General purpose NO and NC relay
contacts.
6
RELAY # 1 NO
7
RELAY # 1 RTN
8
RELAY # 2 NC
General purpose NO and NC relay
contacts.
9
RELAY # 2 NO
10
RELAY # 2 RTN
TB6
1
Bypass
∅
A
Optional Powerware 9315 Sync Control
Control Connections
2
Bypass
∅
B
3
Bypass
∅
C
4
Sync Reference
∅
A
5
Sync Reference
∅
B
6
Sync Reference
∅
C
7
Output
∅
A
8
Output
∅
B
9
Output
∅
C
TB7
1
+12VDC
Optional CAN Power Supply Panel (A13)
Terminal Block for Powerware 9315
(500 kVA−750 kVA) Models only
2
+12VDC RTN
3
+12VDC
4
+12VDC RTN
5
+12VDC
6
+12VDC RTN
7
+12VDC
8
+12VDC RTN
9
+12VDC
10
+12VDC RTN