DESCRIPTION:
DRAWING NO:
3 of 6
INSTALLATION NOTES
SHEET:
NOTE: Customer ground, size 2/0, can be
run in any conduit listed in Table C.
164201150−1
A−4
EATON
Powerware 9315 Parallel Capacity/Redundant System
164201150 Rev. E
www.powerware.com
Table C. Power Cable Terminations and Conduit Requirements
Powerware 9315 1200A System Bypass Module
Terminal Function
Terminal
Function
Bus Landings
Tightening
Torque
N-M (lb-ft)
Bolt/Int.
Hex Size
(In.)
AC Input from UPS
Output to SBM
E8
Phase A
8 − 2 bolt mounting
76 (56)
1/2
E9
Phase B
8 − 2 bolt mounting
76 (56)
1/2
E10
Phase C
8 − 2 bolt mounting
76 (56)
1/2
AC Input to SBM
Bypass
E1
Phase A
8 − 2 bolt mounting
76 (56)
1/2
E2
Phase B
8 − 2 bolt mounting
76 (56)
1/2
E3
Phase C
8 − 2 bolt mounting
76 (56)
1/2
AC Input from SBM
to optional SMB
E8
Phase A
4 − 4/0-500 kcmil
Pressure Termination
42.4(32.2)
3/8
E9
Phase B
4 − 4/0-500 kcmil
Pressure Termination
42.4(32.2)
3/8
E10
Phase C
4 − 4/0-500 kcmil
Pressure Termination
42.4(32.2)
3/8
AC Input to
optional SMB
Bypass
E1
Phase A
4 − 4/0-500 kcmil
Pressure Termination
42.4(32.2)
3/8
E2
Phase B
4 − 4/0-500 kcmil
Pressure Termination
42.4(32.2)
3/8
E3
Phase C
4 − 4/0-500 kcmil
Pressure Termination
42.4(32.2)
3/8
AC Output from
SBM or optional
SMB to Critical
Load
E5
Phase A
8 − 2 bolt mounting
76 (56)
1/2
E6
Phase B
8 − 2 bolt mounting
76 (56)
1/2
E7
Phase C
8 − 2 bolt mounting
76 (56)
1/2
SBM Neutral
E4
Neutral
26 − 2 bolt mounting
76 (56)
1/2
SBM Customer
Ground
Frame
Ground
Ground
26 − 1 bolt mounting
76 (56)
1/2
SMB Neutral
E4
Neutral
8 − 2 bolt mounting
76 (56)
1/2
SMB Customer
Ground
Frame
Ground
Ground
14 − 1 bolt mounting
76 (56)
1/2