Powerware 9315 Parallel Capacity/Redundant System
164201150 Rev. E
www.powerware.com
13.5.3 Meters Printout (Ctrl + M)
This key sequence prints the current readings of the SBM system meters. The
Input area shows the phase-to-phase voltage, frequency, and phase current of the
incoming utility, followed by the kVA, kW, and power factor measurements. The
output area shows the same information for the power being output by the SBM.
The Bypass area shows the phase-to-phase voltage of the bypass source. The
Battery area displays the DC voltage (V) and the DC current (I). Figure 13−5
shows a sample Meters printout.
Input
Output
Bypass
Battery
VAB
480
VBC VCA
KW
505
KVA
530
IA
IB
IC
FREQ
60.0
PF
0.95
V
540
I
0
640
480 480
640
640
VAB
480
VBC
VCA
480
480
IA
IB
IC
480
480
480
IN
0
VAB
480
VBC
VCA
480
480
FREQ
60.0
KVA
400
KW
320
PF
0.80
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
03 NOV 1997 14:22:45
+
Figure 13−5.
System Meters Screen
13.5.4 System Information Printout (Ctrl + A)
This key sequence prints a listing of all available serial data. This printout contains
the information shown on the Event History Log and Meters screens of the SBM
(both Figures 13−4 and 13−5).