![Eaton 9315 Скачать руководство пользователя страница 148](http://html.mh-extra.com/html/eaton/9315/9315_installation-and-operation-manual_527095148.webp)
DESCRIPTION:
DRAWING NO:
5 of 6
INSTALLATION NOTES
SHEET:
164201150−1
A−6
EATON
Powerware 9315 Parallel Capacity/Redundant System
164201150 Rev. E
www.powerware.com
12.
Bypass input overcurrent protection and Bypass input disconnect switch are to be
provided by the user. Table E lists the maximum rating for output circuit breakers
satisfying the criteria for both. Rating is based on 125% of output current for an 80%
breaker.
Table E. Maximum Bypass Input Circuit Breaker Ratings
Powerware 9315
System Bypass
module
SBM Model
600
800
1000
1200
1600
2000
1200A SBM
750
1000
1250
1500
N/A
N/A
2000A SBM
N/A
N/A
N/A
1500
2000
2500
13.
Local code may require UPS module output overcurrent protection. Refer to the applicable
UPS manual for UPS module output overcurrent protection breaker size.
14.
The breakers CBS, CBP and FBP have a AT trip ratings and a maximum Amp Interrupting
Capability (KAIC) as shown in Table F.
Table F. SBM Breaker Trip Ratings and Amp Interrupting Capability
Powerware 9315
System Bypass
module
SBM Model
600
800
1000
1200
1600
2000
All Models
Trip Rating
KAIC
1200A SBM
600
800
1000
1200
N/A
N/A
35
2000A SBM
N/A
N/A
N/A
1200
1600
2000
65
15.
Output overcurrent protection and output disconnect switch are to be provided by the
user. Table G lists the maximum rating for output circuit breakers satisfying the criteria
for both. Rating is based on 125% of output current for an 80% breaker.
Table G. Maximum Output Circuit Breaker Ratings
Powerware 9315
System Bypass
module
SBM Model
600
800
1000
1200
1600
2000
1200A SBM
750
1000
1250
1500
N/A
N/A
2000A SBM
N/A
N/A
N/A
1500
2000
2500
16.
In the Parallel Capacity/Redundant System, each UPS module, System Bypass Module
(SBM) and optional equipment are crated separately for shipping.
17.
Do not tilt cabinets more than
10° during handling.
18.
Dimensions are in millimeters (inches).
Содержание 9315