G. Uncomfortable
temperature.
(Not enough
heat/cold air)
(cont’d)
7. Refrigerant undercharged.
7. Check for refrigerant level in
ACC.(Heating mode only)
Repair leak, evacuate and recharge the
system. Check In-line sight glass in
cooling mode.
8. Restriction in refrigerant circuit.
8. Check for blockage or restriction,
especially in Liquid Flow Control.
Assure that modification of non-ETI air
handler is performed.
Check valves,
filter/dryer and anti-migration valve.
9. System is locked out on high or
low pressure.
9. Check low pressure and high pressure:
Check limit cut-off pressures. Control
is set to actuate at 5 (R-22 &
407C)/25psig (R-410A) (low pressure)
and 400 (R-22 & 407C)/600 psig (R-
410A) (high pressure) +10%. Check for
continuity on both switches under
normal pressure conditions. Refer to
Unit performance table.
10. Defective pressure control.
10. Check limit cut-off pressures. Control
is set to actuate at 5 (R-22 &
407C)/25psig (R-410A) (low pressure)
and 400 (R-22 & 407C)/600 psig (R-
410A) (high pressure) +10%. Check for
continuity on both switches under
normal pressure conditions.
11. Reduced air flow.
11. Check air ducts for leaks and repair.
Check blower operation. Check air
filter(s). Remove air flow restrictions
(min.400 CFM/ton).
12. Unit undersized/ oversized.
12. Contact ETI Technical Support at 863-
701-0096.
H. Poor Compressor
Performance
(Runs, but Not
pumping
Refrigerant)
1. Reversing Valve stuck and
Compressor will not create a
pressure difference between high
and low side of the system.
1a. Pinch closed the Discharge Line to
verify the Compressor builds High
Pressure, if so, replace Reversing
Valve.
1b. If High pressure does not build after
pinching the Discharge Line closed, the
Compressor has failed, replace
Compressor.
2. Bad Compressor
2. Replace after verification of Amp Draw
below RLA and pinch closed the
Discharge Line between the
Compressor and the reversing Valve to
verify pressure does not build on the
high side.
Figure 36. System
Troubleshooting Chart (con’t)
Содержание Prime-025
Страница 15: ...PSD QS 02 16 Page 15 Figure 8 PSD Compressor Unit Electrical Schematic 230 1 60...
Страница 16: ...PSD QS 02 16 Page 16 Figure 9 PSD Compressor Unit Electrical Schematic 230 3 60...
Страница 17: ...PSD QS 02 16 Page 17 Figure 10 PSD Air Heating Cooling Water Heating Application...
Страница 18: ...PSD QS 02 16 Page 18 Figure 11 PSD Air Heating CoolingWater Heating Field Wiring Diagram...
Страница 20: ...PSD QS 02 16 Page 20 Figure 11a SureStart Mode of Operation...
Страница 27: ...PSD QS 02 16 Page 27 Figure 15 Disassembled Plug Connector...
Страница 34: ...PSD QS 02 16 Page 34 Figure 24 PSD Internal Flow Schematic...
Страница 35: ...PSD QS 02 16 Page 35 Figure 25 PSD Piping...
Страница 37: ...PSD QS 02 16 Page 37 Figure 26 Evacuation of PSD System...
Страница 39: ...PSD QS 02 16 Page 39 Figure 27 Initial Charge of PSD System...
Страница 41: ...PSD QS 02 16 Page 41 Figure 28 Final Charge of PSD System...
Страница 42: ...PSD QS 02 16 Page 42 Figure 29 Charging to the Middle Sight Glass Figure 30 Charging to the Top Sight Glass...
Страница 44: ...PSD QS 02 16 Page 44 Figure 32 Start Up Process...
Страница 53: ...PSD QS 02 16 Page 53...
Страница 54: ...PSD QS 02 16 Page 54...
Страница 55: ...PSD QS 02 16 Page 55...
Страница 56: ...PSD QS 02 16 Page 56...
Страница 57: ...PSD QS 02 16 Page 57...
Страница 58: ...PSD QS 02 16 Page 58...