PSD-QS (02/16)
Page 38
3)
Initial Charge
1. Disconnect the vacuum pump and isolate the digital vacuum gage. Connect the refrigerant
container to the charging hose of the manifold gage set as shown in Figure 27.
2. Place the refrigerant container upside down, with the refrigerant valve at the bottom, on the
scale, as shown in Figure 27. Purge the charging hose by loosending it at the manifold end,
until refrigerant is released. Tighten the charging hose and zero out the refrigerant scale.
3. Open the LP valve on the manifold gage set. Opening the refrigerant container valve sends
liquid refrigerant through the initial charging port into the system.
Continue to add refrigerant
until 3 pounds per ton of system capacity has been added.
In cold weather, it may be
necessary to warm the refrigerant container to charge to 3 pounds per ton.
4. After completing the initial refrigerant charge to the system, turn the LP valve off, re-install the
Schrader valve core into the initial charging port, remove the tool, and install the Schrader
valve cap firmly on the Schrader valve.
WARNING!
Inhalation of high concentrations of refrigerant gas vapor is harmful and
may cause heart irregularities or death. Vapor reduces oxygen available
for breathing and is heavier than air. Decomposition products are
hazardous. Liquid contact can cause frostbite. Avoid contact of liquid
with eyes and prolonged skin exposure. Liquid and gas are under
pressure. Deliberate inhalation of refrigerant gas is extremely
dangerous. Asphyxiation can occur without warning due to lack of
oxygen. Before using, read the material safety data sheet. Use proper
safety measures when charging the system, especially when warming
the refrigerant container. Do not overheat.
Содержание Prime-025
Страница 15: ...PSD QS 02 16 Page 15 Figure 8 PSD Compressor Unit Electrical Schematic 230 1 60...
Страница 16: ...PSD QS 02 16 Page 16 Figure 9 PSD Compressor Unit Electrical Schematic 230 3 60...
Страница 17: ...PSD QS 02 16 Page 17 Figure 10 PSD Air Heating Cooling Water Heating Application...
Страница 18: ...PSD QS 02 16 Page 18 Figure 11 PSD Air Heating CoolingWater Heating Field Wiring Diagram...
Страница 20: ...PSD QS 02 16 Page 20 Figure 11a SureStart Mode of Operation...
Страница 27: ...PSD QS 02 16 Page 27 Figure 15 Disassembled Plug Connector...
Страница 34: ...PSD QS 02 16 Page 34 Figure 24 PSD Internal Flow Schematic...
Страница 35: ...PSD QS 02 16 Page 35 Figure 25 PSD Piping...
Страница 37: ...PSD QS 02 16 Page 37 Figure 26 Evacuation of PSD System...
Страница 39: ...PSD QS 02 16 Page 39 Figure 27 Initial Charge of PSD System...
Страница 41: ...PSD QS 02 16 Page 41 Figure 28 Final Charge of PSD System...
Страница 42: ...PSD QS 02 16 Page 42 Figure 29 Charging to the Middle Sight Glass Figure 30 Charging to the Top Sight Glass...
Страница 44: ...PSD QS 02 16 Page 44 Figure 32 Start Up Process...
Страница 53: ...PSD QS 02 16 Page 53...
Страница 54: ...PSD QS 02 16 Page 54...
Страница 55: ...PSD QS 02 16 Page 55...
Страница 56: ...PSD QS 02 16 Page 56...
Страница 57: ...PSD QS 02 16 Page 57...
Страница 58: ...PSD QS 02 16 Page 58...