Product Manual Oria Thermostat
EAE KNX Oria Thermostat
Oria Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Sayfa
35
/ 50
Heating control parameters for on/off controller type should be configured here. For more information about
on/off controller read Chapter 4.4.3.3.
4.4.4.3.1
Parameters
Parameter
Setting
Description
Cyclic Interval
1…
5
…255
Time period to send heating
control value over “Heating
Control Value” communication
object.
Inverse Output
Enable /
Disable
Invert the output of the controller.
For example if normal output is
“On”, then inverted output is
“Off”.
Hysteresis (1/10 K)
1…
30
…255
Hysteresis value (Chapter 4.4.3.3)
Table 33
4.4.4.3.2
Communication Objects
No
Object Name
Function
Data Type
Flags
61
Heat Control Value Send
1 bit
DPT 1.002
CT
Heating actuator will be controlled through this communication object.
Table 34
4.4.4.4
Fan Coil
Figure 17
Heating control parameters for fan coil controller type should be configured here. For more information about
on/off controller read Chapter 4.4.3.4.