4.4.4.5.1
Parameters
Parameter
Setting
Description
Cyclic Interval
1…
5
…255
Time period to send heating
control value over “Heating
Control Value” communication
object.
Send On/Off at Control Mode
Switchover
Enable
/ Disable
Enables “Split Heat”
communication object, can be
used to open/close the split unit
when a control mode change
occurs.
Communication Error Object
Enable /
Disable
Enables “Split Heat Error”
communication object. “True”
telegram from this communication
objects cause thermostat to enter
“Protection Mode” with error. (For
more information Chapter 4.5.2)
Table 37
4.4.4.5.2
Communication Objects
No
Object Name
Function
Data Type
Flags
51
Split Heat
On/Off
1 bit
DPT 1.001
CT
Visible if “Send On/Off at Control Mode Switchover” parameter enabled. This communication object is not a
control object, it will send “True” when control mode is “Heat” and “False” when control mode is “Cool” and
can be used to enable the split unit.
53
Split Heat Error
True/False
1 bit
DPT 1.002
CW
Visible if “Communication Error Object” parameter enabled. “True” telegram causes the thermostat to enter
“Protect Mode wit Error” and thermostat stay in this state until “False” telegram received (For more
information Chapter 4.5.2).
Table 38
4.4.5 Cooling Control
Selection of the cooling control type, parameters of the selected control type should be configured here.