4.4.5.4 Fan Coil
Figure 22
Cooling control parameters for fan coil controller type should be configured here.
4.4.5.4.1
Parameters
Parameter
Setting
Description
Cyclic Interval
1…
5
…255
Time period to send cooling
control value over “Cool Control
Value” communication object.
Inverse Output
Enable /
Disable
Invert the output of the controller.
For example if normal output is
%80, then inverted output is %20.
Proportional Gain KP
1…
66
…255
Proportional gain of PI algorithm
Integral Gain KI (1/1000)
1…
32
…255
Integral gain of PI algorithm, given
value divided by 1000.
Maximum Control Signal (%)
0…
100
Maximum control signal value.
Minimum Control Signal (%)
0
…100
Minimum control signal value
Transmit on Modification
Enable
/ Disable
When control signal change more
than (%4), cooling control value
will be transmitted over “Cooling
Control Value” communication
object.
Table 45
4.4.5.4.2
Communication Objects
No
Object Name
Function
Data Type
Flags
61
Cool Control Value Send
1 bit
DPT 1.002
CT
Cooling actuator will be controlled through this communication object.
Table 46