Product Manual Oria Thermostat
EAE KNX Oria Thermostat
Oria Thermostat PM R1.0
©
EAE Technology
www.eaetechnology.com
Sayfa
21
/ 50
4.2.2.2
Switch and Dim
Figure 9
When push button function selected as “Switch and Dim” push button can be configured in three different
ways to control brightness value.
Short Press
Long press
Darker(Short Press Off)
Off (%0)
Decrease, (%XX)
Brighter(Short Press On)
On(%100)
Increase,(%XX)
Darker/Brighter(Short Press Toggle) Toggle between Darker/Brighter Decrease, (%XX) / Increase,(%XX)
Table 18
%XX values can have different values relative to the “Dimming Type” parameter. “Dimming Type” parameter
allows two different types of dimming functionality “Start Stop” and “Step Wise”.
Dimming - Start Stop Type
When push button pressed (and not released) and pressed duration exceeds “Long Press Duration” time
“Increase, %100” (When button in Brighter mode) or “Decrease, %100” (When button in Darker mode)
dimming level will be send using respective communication object. When button released “Increase, Break” or
“Decrease, Break” value will be send.
Dimming - Step Wise Type
When push button pressed (and not released) and pressed duration exceeds “Long Press Duration” time, a step
value level configured in “Step Value” parameter will be send using respective communication object. If button
mode is “Darker”, “Decrease, % [Step Value]”, else button mode is “Brighter”, “Increase, % [Step Value]” values
will be send. Until button is released same step value will be send periodically with a time interval defined in
“Step Send Interval”.