Error
Enter Error Mode Condition
Leave Error Mode Condition
Window Status
Open
Close
Split Heat Error
True
False
Split Cool Error
True
False
Table 48
When in error mode if another error condition occurs, thermostat will stay in error mode until both errors are
fixed.
4.5.3 Reset on Site
Reset on site operation resets the default setpoint temperatures and fan speeds for Comfort, Night and Away
modes to their original value which downloaded when commissioned using ETS.
4.5.4 Parameters
Parameter
Setting
Description
Send Setpoint
Cyclic
/ Cyclic and Change
Selects whether setpoint will be send
periodically or periodically and change.
If selected as change, minimum
difference that will trigger a
transmission is defined in “Minimum
Difference” parameter in
“Temperature Sensor” tab.
Cyclic Time (in sec)
10…
30
…65535
Cyclic time period to send setpoint
from “Current Setpoint”
communication object.
Step Value
0,1 /
0,5
/ 1
Increase/Decrease value of current
setpoint when “Setpoint Buttons” on
thermostat is pressed.
Allowed Range
0…
5
…30
Setpoint limitations relative to the
operating modes setpoint. (For more
information - Chapter 4.5.1)
Maximum Setpoint
0…
40
…99
Maximum absolute setpoint limitation
(For more information - Chapter 4.5.1).
Minimum Setpoint
0
…99
Minimum absolute setpoint limitation
(For more information - Chapter 4.5.1).
Reset on Site
Enable
/ Disable
Enables reset on site operation which
resets the default setpoint
temperatures and fan speeds to their
original value which downloaded when
commissioned using ETS.
Reset on Site Value
0
/ 1 / Any Value
Select the “Reset on Site”
communication object value that will
trigger reset on site operation
Comfort Mode
Setpoint
0…
25
…99
Comfort mode setpoint value
Fan Speed
Fan Speed 1 / Fan Speed 2 /
Fan Speed 3 /
Auto
Comfort mode fan speed value
Night Mode